Air pressure switch

This is used to check whether the fumes are adequately evacuated. The pressure switch compares the
static and dynamic signals coming from the pressure test points on the fan according to the figure. The
pressure switch is connected to the card and is normally open (see diagram). Before the card initiates the
ignition procedure (opening the valve, etc.), you must make sure that the fan works properly and that the
air pressure switch ensures this by closing its contacts. This happens if the difference in pressure is
165±15Pa. So the signal must be at least 180Pa. To open its contacts again, the difference in pressure must
drop under 150±13Pa. To perform checks on contact opening and closing, it is always recommended to
check directly on the card (X5 - 3/4).
Checks
It is necessary to check:
Whether the electrical connections are correct.
Whether the pressure test point pipes are clean and contain no condensation water.
That the signal is open when the fan is not working.
That the pressure is at least 180Pa and that above this pressure the pressure switch closes its
contacts.
If the signal is low, it is necessary to check that the fume diaphragm is correct, the fan has 230V, the
pressure test points are properly inserted and the Venturi tube has no burrs of any kind. Lastly, check
that the ends of the pipes are not obstructed.
N.B. The pressure difference must be measured with the airtight chamber closed. The pressure gauge
connections can come out through the hole, which is closed by a silicone plug, on the front of the cover.
24
Supplied By www.heating spares.co Tel. 0161 620 6677
DOMINA F 24 - 30 E
FERELLA F 24 - 30 MEL
MILOS AIR COMPACT E
Key
NO
=
Normally open
NC
=
Closed
C
=
Common
Version - 09.2002

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ferella f 24-30 melMilos air compact e

Table of Contents