27 FLUE TERMINAL POSITION

The terminal should be positioned so that products of
combustion can safely disperse at all times.
Pluming may occur at the termination so, where
possible, terminal positions where this could cause
a nuisance should be avoided.
Minimum dimensions are shown below
300mm
min
Flat roof - with structure
26
INSTALLATION
m
0 m
3 0
i n
m
625mm
Fixed
Terminal Position
Directly below an opening,
air brick, windows, etc.
Below plastic / painted gutters
Painted surface
Below eaves or balcony
3 0 0 m m
m i n
Minimum Dimension
300 mm
300 mm
300 mm
500 mm
Esprit -
690mm
Fixed
Installation and Servicing