Liebert Integrated Secured Protection User Manual

Liebert integrated secured protection user manual

Advertisement

Quick Links

Little Glass House
Integrated Secured Protection
for Network Equipment
U
M
SER
ANUAL
English

Advertisement

Table of Contents
loading

Summary of Contents for Liebert Integrated Secured Protection

  • Page 1 Little Glass House Integrated Secured Protection for Network Equipment ANUAL English...
  • Page 2: Table Of Contents

    SAFETY INSTRUCTIONS ... 3 GLOSSARY OF SYMBOLS... 3 INTRODUCTION ... 4 UPS SUPPORT... 5 INSTALLATION... 5 UNLOADING AND INSPECTION ... 5 LOCATION... 5 INSTALLATION CONNECTIONS ... 6 INSTALLING CUSTOMER EQUIPMENT... 6 START-UP ... 7 OPERATION ... 8 ENVIRONMENTAL CONTROL MODULE (ECM) & UNINTERRUPTIBLE AIR SUPPLY™ (UAS)... 8 FORCED AIR COOLING (FAC)...
  • Page 3: Safety Instructions

    SAVE THESE IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself. Opening or removing covers will risk exposure to dangerous voltages. Refer all servicing to qualified service 1. SAVE THESE INSTRUCTIONS. MANUAL CONTAINS SAFETY INSTRUCTIONS. Read all safety and operating instructions before operating the Little Glass House (LGH).
  • Page 4: Introduction

    Your Liebert Little Glass House™ (LGH) will provide a secure controlled environment in a single factory assembled enclosure. integrated/matched models are designed to control the environment and provide smooth reliable power so that your sensitive computer and network equipment will provide the reliable performance you depend upon for your business operations.
  • Page 5: Ups Support

    1/4 turn to open. Inspect exterior and interior for shipping damage. If any damage is noted, file a claim with the shipper and inform your Liebert supplier. LOCATION The unit should be located in a room where the ambient air is adequately ventilated for the peripheral equipment (printers, etc.) outside the...
  • Page 6: Installation Connections

    Bottom Non-Restricted The unit can be rolled forward on casters for easy access to Liebert and customer wiring at the rear of the unit. To open the front door, clearance required depends on the size of your unit. No side clearance is needed.
  • Page 7: Start-Up

    UPS operation and LED indicators. CAUTION: To maintain UPS battery capacity, do not store Little Glass House for more than 6 months without applying power. Call your Liebert supplier if you have any questions or problems during the installation or operation your...
  • Page 8: Operation

    UNINTERRUPTIBLE POWER SUPPLY (UPS) The Little Glass House may be supplied with one of several Liebert UPS units, or with no UPS. For integrated/matched models, the UPS and ECM are normally sized with matched capacities.
  • Page 9: Sensor Options

    An optional UPS status communication cable is available that allows transmission of information between the UPS and the SiteNet Integrator. This cable will plug into the 25 pin D Type connector on the rear of the UPS marked DB- 25P. The opposite end of the cable in plugged into the 9 pin D Type receptacle on the rear of the SiteNet Integrator marked UPS RS-232 DB- SENSOR OPTIONS...
  • Page 10: Maintenance

    Environmental Control Module can be pulled forward after removing four rack mount screws. -Replace cable access cover on ECM. Package unit for return to Liebert. -Install the replacement ECM. MAINTENANCE UPS REPLACEMENT To remove the UPS for factory repairs: -Turn off power.
  • Page 11: Tables

    FORCED AIR COOLING (FAC) PERFORMANCE DATA (WITH 30PPI FILTER) AIRFLOW (w/Filter) # FANS HIGH MODEL # SPEED 190 CMF FAC-190 112 CMH 360 CMF FAC-360 212 CMH ENVIRONMENTAL COOLING MODULE (ECM) PERFORMANCE DATA MODEL RATED SUPPORT RATED/MAX NUMBER CAPACITY LOAD BTUH/Watt BTUH/Watt 60Hz...
  • Page 12: Fixed Service Connection (Amps)

    Electrical Service / Connection The 60 Hz LGH is provided with a single NEMA plug and cord input power connection (except for ECM- 80 systems). 60 Hz Systems with UPS - Service Connection If a UPS is supplied, the system power rating and plug connection are fixed. FIXED SERVICE CONNECTION (AMPS) Cooling System...
  • Page 13: Drawings

    DRAWINGS...
  • Page 21 LGH RD/HD FORCED AIR CABINET TEMP. RISE AT STANDARD AIR CONDITIONS FAC-360(2 FAN) HIGH SPEED FAC-190(1 FAN) HIGH SPEED FAC-360(2 FAN) LOW SPEED FAC-190(1 FAN) LOW SPEED INTERNAL LOAD PER CABINET, WATTS MINIMUM SPEED SET AT 2000 RPM 1000 1200 1400...
  • Page 22 INTEGRATOR POWER, UPS, & TERMINAL CONNECTIONS...
  • Page 23: Troubleshooting

    PROBLEM ECM Not Cooling No Power Filter Clogged Refrigerant loss Hot Gas Bypass Valve set incorrectly Squirrel cage free spinning on evaporator or condenser blowers Clogged Condenser coil Fans blowing warm air Compressor trips on thermal overload. Faulty Compressor Condensate draining Excessive opening of doors continuously Enclosure not properly sealed...
  • Page 24 Liebert supplier with the unit model number and serial number. He will obtain the required warranty return authorization from Liebert Corporation. Customer is to package and ship the defective module or part to Liebert as outlined on the Warranty Return Tag. The Warranty Return Tag needs to be completed with description of defect, installer's name and telephone number, and must accompany the defective module or part back to Liebert.
  • Page 25 Outside the U.S.A. Worldwide FAX tech support The Company Behind The Products With more than 500,000 installations around the globe, Liebert is the world leader in computer protection systems. founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics: §...