Download Print this page
Liebert  LPGE Series Technical Specifications
Liebert  LPGE Series Technical Specifications

Liebert LPGE Series Technical Specifications

Panel guard extension

Advertisement

Quick Links

Model # LPGE _ _ _ _ _ _ _ _ - _ _
Voltage
Surge Rating
120S
Per Mode
120Y
65kA
230Y
80kA
277Y
100kA
Monitoring Options
LED only, Standard
Audible Alarm
Audible Alarm & Transient Counter
Job Name____________________________
Model# ______________________________
Date ________________________________
Qty _________________________________
Quote# ______________________________
Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169
EMAIL: info@control-concepts.com • Web Site: www.Liebert.com
Liebert Panel Guard Extension (LPGE Series)
Modes of Protection ..................All (L-N, L-L, L-G, N-G Wye &
50
Status Indication ........................LEDs, Dry Contacts
Certifications ..............................UL 1449 & 1283, CSA, ISO 9001
Enclosure ...................................NEMA 1
Warranty .....................................5 Years
Shipping Weight.....................15 lb.
LPGE120Y100F-01
Example Part Number:
277/480V, 3-Phase Wye, 100kA Per Mode, 200kA Per
Phase, Flush Mount Enclosure, LED's, Audible Alarm,
Transient Counter, Form C Contacts
Enclosure
65
Surface
S
80
Flush
F
100
00
02
01
Technical Specification
EMI/RFI Attenuation ..........10 kHz-100MHz
UL 1449 second edition clamping data
Voltage
120/208
120/240
230/400
208, 240, 277
277/480
Life Cycle Surge Testing
10kA, 20kV, IEEE Cat. C3
Unit
Per Mode (L-N/L-G/N-G)
65kA
6,000 / 6,000 / 6,000
80kA
8,000 / 8,000 / 8,000
100kA
10,000 / 10,000 / 10,000
Universal Panelboard application –
can be used with most major
manufacturers.
Flexible mounting (top, bottom or
adjacent) to virtually any panelboard.
Complete UL 1449 and UL1283
listed product.
Surge current capacity levels from
130kA per phase to 200kA per
phase.
Standard features include all modes
of protection, unit status indicators
and isolated Form C dry contacts.
Options include: audible alarm,
transient counter.
L-L, L-G Delta) where applicable
60 dB Max
L-N
L-G
L-L
400
400
800
400
400
800
800
800
1500
800
800
1500
800
800
1500
Per Phase
12,000
16,000
20,000
82242 Rev 0
N-G
400
400
800
800
800

Advertisement

loading