Table 8 Liebert Psi Xr Battery Run Times - Liebert UPS Systems PSI XR User Manual

Psi xr 1000/1500/1920/3000va, 60hz, 120vac
Hide thumbs Also See for UPS Systems PSI XR:
Table of Contents

Advertisement

Table 8
Liebert PSI XR battery run times
Number of Batteries
Internal Battery
Internal Battery
+ 1 External
Battery Cabinets
Internal Battery
+ 2 External
Battery Cabinets
Internal Battery
+ 3 External
Battery Cabinets
Internal Battery
+ 4 External
Battery
Cabinets
Internal Battery
+ 5 External
Battery Cabinets
Internal Battery
+ 6 External
Battery Cabinets
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
Load %
1000VA
10
82
25
43
50
15
75
9
100
6
10
272
25
139
50
73
75
51
100
31
10
438
25
231
50
129
75
84
100
65
10
614
25
324
50
181
75
126
100
96
10
789
25
385
50
233
75
162
100
124
10
964
25
509
50
285
75
197
100
151
10
1140
25
601
50
336
75
233
100
179
23
1500VA
1920VA
81
76
32
32
13
14
8
8
5
5
222
161
109
80
55
45
31
25
18
15
357
241
175
128
95
67
61
47
46
29
492
322
241
170
131
95
84
62
64
48
627
483
308
255
167
143
114
100
82
72
762
564
374
298
203
167
139
116
106
84
897
644
440
341
239
191
163
133
124
102
Specifications
3000VA
75
32
13
8
5
142
70
31
17
12
205
106
56
31
18
267
139
73
50
31
329
171
95
62
47
392
204
113
74
56
454
236
131
85
65