Liebert PowerSure PSA 350VA to 1000VA Specifications

Liebert single - phase uninterruptible power supply systems specification sheet

Advertisement

Quick Links

Liebert PowerSure PSA UPS
GUIDE SPECIFICATIONS
350VA to 1000VA
Single - Phase Uninterruptible Power Supply Systems
1.1
SUMMARY
This specification defines the electrical and mechanical characteristics and requirements for a continuous-
duty single-phase, solid-state, uninterruptible power system. The uninterruptible power system, hereafter
referred to as the UPS, will provide high-quality AC power for sensitive electronic equipment loads.
1.2
STANDARDS
The UPS is designed in accordance with the applicable sections of the current revision of the following
documents. Where a conflict arises between these documents and statements made herein, the statements
in this specification will govern.
120V Units
UL 1778, c-UL listed (to CSA 22.2 No. 107.1)
FCC Part 15, Subpart B, Class B
ANSI C62.41, Category A, Level 3 (IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria A
EN61000-4-2, Level 3, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN61000-4-6, Level 3, Criteria A
EN61000-3-2
EN61000-3-3
ISTA Procedure 1A
230V Units
EN50091-1-1, TUV/GS listed, CE compliance mark
EN50091-2, Class B
EN61000-4-2, Level 3, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6
EN61000-4-4, Level 4, Criteria A
EN61000-4-5, Level 3, Criteria A
EN61000-3-2
EN61000-3-3
ISTA Procedure 1 A
1.3.
SYSTEM DESCRIPTION
1.3.1
Modes of Operation
The UPS is designed to operate as a line-interactive system in the following modes:
A. Normal - The critical AC load is continuously supplied with filtered power. The battery
charger maintains a float-charge on the battery.
PowerSure PSA
350 – 1000VA
1.0
GENERAL
1
Guide Specification
SL-23271 8/03

Advertisement

loading

Summary of Contents for Liebert PowerSure PSA 350VA to 1000VA

  • Page 1 Liebert PowerSure PSA UPS GUIDE SPECIFICATIONS 350VA to 1000VA Single - Phase Uninterruptible Power Supply Systems SUMMARY This specification defines the electrical and mechanical characteristics and requirements for a continuous- duty single-phase, solid-state, uninterruptible power system. The uninterruptible power system, hereafter referred to as the UPS, will provide high-quality AC power for sensitive electronic equipment loads.
  • Page 2 B. Voltage Boost/Buck - During input power source abnormalities (sags and swells), the AC output power is corrected by means of boost (sag correction) or buck (swell correction) compensation taps. Operation of the compensation taps automatically maintains the proper output voltage for the connected critical equipment. The compensation taps is designed for indefinite operation to their limits.
  • Page 3 127 VAC nominal: single phase, 2-wire-plus-ground: 90 ─ 150 VAC (±3VAC), Buck compensation: 141VAC (±3VAC) Boost1 compensation: 113VAC (±3VAC) Boost2 compensation: 100VAC (±3VAC) 220 VAC nominal: single phase, 2-wire-plus-earth: 155 ─ 270 VAC (±6VAC) Buck compensation: 243 VAC (±6VAC) Boost1 compensation: 197 VAC (±6VAC) Boost2 compensation: 174 VAC (±6VAC) 230 VAC nominal: single phase, 2-wire-plus-earth: 163 ─...
  • Page 4: Environmental Conditions

    Voltage Transient Response: ±15% in Normal mode for 0-100-0% loading of the UPS rating, ±5% in Battery mode for 20-100-20% loading of the UPS rating. Transient Recovery Time: To within ±8% of nominal voltage in < 2 cycles. Efficiency: >95% (Normal mode) >90% (Buck/Boost mode) Output Power Cords: The 230 VAC units have two (2) detachable IEC-320-C14 output power cords measuring 2m (6.6 ft) in length.
  • Page 5 QUALITY ASSURANCE 1.7.1 Manufacturer Qualifications Liebert Corporation provides more than twenty years experience in the design, manufacture, and testing of solid-state UPS systems and the company is certified to ISO 9001. 1.7.2 Factory Testing Before shipment, the product is tested to assure compliance with the specification.
  • Page 6 2.2.2 Bi-Directional Converter 2.2.2.1 General The Bi-Directional Converter incorporates solid-state devices and control circuitry to convert AC power to regulated DC power for battery charging; and convert DC power from the battery to regulated and conditioned stepped-sinewave AC power for supporting the critical load.
  • Page 7 2.2.3 Display and Controls 2.2.3.1 General The UPS is provided with a microprocessor-based unit status and control display designed for convenient and reliable user operation. The status and alarm indicators are displayed on a status indicator display. 2.2.3.2 System Indicators There are three (3) status indicators on the front of the UPS (Utility, Battery and Fault) and one (1) on the rear (Site Wiring Fault): The Utility Indicator illuminates when the UPS is operating and supplying...
  • Page 8 MultiLink™ software. The DB-9 is capable of supplying serial communication, on battery and low battery signals. MultiLink, Liebert’s UPS monitoring and shutdown software, is shipped with the UPS, along with a 10-ft. (3m) DB-9 cable required for running MultiLink.

This manual is also suitable for:

Powersure psa 350vaPowersure psa 500vaPowersure psa 650vaPowersure psa 1000va