Carrier 40GJ Owner's Manual page 9

Cassette ductless split system sizes 12 to 24

Advertisement

Install of The Compact Panel Cassette Type Indoor Unit
Smear freeze motoroil
here
Torque wrench
Flare nut
Form 1: The tightening torque needed for tightening nut
Diameter Inch
''
''
''
''
''
Drainage hose
1. Install the drain hose
The diameter of the drain hose should be equal or bigger than the connection pipe's. ( The diameter of
polythene pipe: Outer diameter 1 in (25 mm) Surface thickness
Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air
bubble.
If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
To prevent bent of the drain hose, the distance between hoisting stand should is 3.28 to 4.92 ft (1 to 1.5 m).
Use the drain hose and clamp attached. Insert the drain hose to the drain vent, and then tighten the
clamp.
Entwine the big sponge on the clamp of drain hose to insulate heat.
Heat insulation should be done to indoor drain hose.
Thread fasten(x4)
Spanner
Wiring interface
Liquid inlet tube
Fig.5
Surface thickness in/mm
0.02 in (0.5 mm)
0.03 in (0.71 mm)
0.04 in (1 mm)
0.04 in (1 mm)
0.04 in (1 mm)
3.28 to 4.92 ft (1 to 1.5 m)
Fig.6
5
Median sponge (attachment)
(entwine the wiring interface
with seal mat)
Heat preservation
sheath of liquid inlet
tube (attachment) (for
liquid tube)
Heat preservation
sheath of gas collection
tube (attachment)(for
Gas collection tube
gas tube)
Tightening torque
20.34~40.68 ft.lb(15~30 N.m)
40.68~54.24 ft.lb(30~40 N.m)
61.02~67.8 ft.lb(45~50 N.m)
81.36~88.14 ft.lb(60~65 N.m)
94.93~101.7 ft.lb(70~75 N.m)
0.06 in (1.5 mm)