Sponge (gray)
Drain stepup pipe note
The install height of the drain raising pipe should less than 11 in (280 mm).
The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond
300mm.
Instruction
The slant gradient of the attached drain hose should be within 3 in (75 mm) so that the drain hole doesn't has
to endure the unnecessary outside force.
Please install the drain hose according to the following process if several drain hoses join together.
2 Check the smoothness of drain after installation.
Check the drain state by immitting 36 3/5 in
Check the drain in the state of refrigerating after installation of the electric circuit.
Install of The Compact Panel Cassette Type Indoor Unit
Sponge(attachment)
Clamp(attachment)
Clamp
Drain hose
Fig.7
11 4/5 in (300 mm)
3.28-4.92
ft (1-1.5 m)
Fig.10
(600 cc) water slowly from the outlet vent or test hole.
3
6
Below 1/6 in (4 mm)
11 in (280 mm)
8 2/3 in (220 mm)