6-3 Pipe connection

Be sure to perform nitrogen permutation or nitrogen blow when
brazing. (Refer to figure 8)
Brazing without performing nitrogen permutation or nitrogen
blow into the piping will create large quantities of oxidized film on
the inside of the pipes, adversely affecting valves and compres-
sors in the refrigerating system and preventing normal operation.
(Refer to figure 8)
1. Refrigerant pipe
2. Location to be brazed
3. Nitrogen
4. Taping
5. Handy valve
6. Regulator
The pressure regulator for the nitrogen released when doing
the brazing should be set to about 0.02 MPa (0.2kg/cm
Enough to feel a slight breeze on your cheek).
Note
Do not use anti-oxidants when brazing the pipe joints.
Residue can clog pipes and break equipment.

6-4 Connecting the refrigerant piping

1.
Direction to bring out the pipes
The local interunit piping can be connected either forward or to
the sides (taken out through the bottom) as shown in the figure 10.
When passing out through the bottom, use the knock hole in the
bottom frame.
(Refer to figure 10)
1. Left-side connection
2. Front connection
3. Right-side connection
Precautions when knocking out knock holes
• Open knock hole in the base frame by drilling the 4 concave
around it with a 6mm bit. (Refer to figure 11)
(Refer to figure 11)
1. Knock hole
2. Drill
3. Concave section (4 points)
• Be sure to avoid damaging the casing
• After knocking out the holes, we recommend you remove any
burrs and paint them using the repair paint to prevent rusting.
• When passing electrical wiring through the knock holes, protect the wir-
ing with a conduit or bushings, making sure not to damage the wiring.
2.
Removing Pinch Piping
When connecting refrigerant piping to an outdoor unit, remove
the pinch piping using the procedure in the figure 12.
(Refer to figure 12)
About handling of shutoff valves, refer to [Shutoff valve opera-
tion procedure] in "11-1 Before working".
Caution
After removing the gass, remove the pinch piping.
Any gas remaining inside may blow off the pinch piping when you dis-
solve the brazing, causing damage.
(Refer to figure 12)
1. Pich piping (4 pieces)
2. Do not remove the relay piping.
3. Pinch piping
4. Procedure 1 : Confirm the shutoff valve is closed.
5. Procedure 2 : Connect a charge hose to the service port
of shutoff valve and remove the gas in the pinch piping.
6. Procedure 3 : After removing the gas in the pinch piping,
dissolve the brazing using a burner and remove the
pinch piping.
3.
Connecting refrigerant piping to outdoor units
• Figure 13 shows the example of connecting refrigerant piping to
outdoor units.
• The local interunit piping next accesorry pipes are field supplyed.
(Refer to figure 13)
1. When connected to the front
2. When connected at lateral side (bottom)
3. Remove the shutoff valve cover to connect.
4. Remove the knock hole on the bottom frame and route
the piping under the bottom frame.
5. Liquid pipe shutoff valve
5
6. Suction gas pipe shutoff valve
7. HP/LP gas pipe shutoff valve
8. Brazing
9. Liquid side accessory pipe (1)
10. Suction gas side accessory pipe (1)
11. HP/LP gas side accessory pipe (1)
12. L type accessory joint (1)
13. L type accessory joint (2)
14. Liquid side accessory pipe (2)
15. Suction gas side accessory pipe (2)
16. HP/LP gas side accessory pipe (2)
17. In case of Q8 type use the Accessory joint for connecting
the Suction gas side accessory pipe (2) to Suction gas
side shutoff valve.
18. Accessory joint
Note
2
• Make sure the onsite piping does not come into contact with other
:
piping or the bottom frame or side panels of the unit.
4.
Branching the refrigerant piping
Heed the restrictions below when installing the refrigerant branch-
ing kit and read the installation instruction manual with the kit.
(Improper installation could lead to malfunctioning or breakdown
of the outdoor unit.)
<REFNET joint>
Install the REFNET joint so it splits horizontally or vertically.
(Refer to figure 14)
1. Horizontal
2. A-arrow view
3. Horizontal surface
4. ±30° or less
5. Vertical
<REFNET header>
Install the REFNET header so it splits horizontally.
(Refer to figure 15)
1. Horizontal surface
2. B-arrow view
English