3. DRY OPERATION

3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 3.
However, the compressor frequency after the start-up is 56rps for 80seconds.
( Table 3 : Compressor frequency )
09LECAN X zone
J zone
Y zone
( Fig.2 : Compressor control based on room temperature )
Room
temperature drops
X zone
Ts+0.5°C
J zone
Ts -1.5°C
Y zone
Operating
speed
30rps
12LECAN
23rps
0rps
Room
temperature rises
Ts+1.5°C
Ts -0.5°C
Operating
speed
X zone
33rps
J zone
25rps
Y zone
0rps
01-03