Cooling Operation - Fujitsu AS* G09LECB Service Instruction

Split type room air conditioner, wall mountedtype inverter
Table of Contents

Advertisement

1. COOLING OPERATION

1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation speed of the compressor.
* If the room temperature is 2°C higher than a set temperature, the compressor operation
speed will attain to maximum performance.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be
stopped.
* When the room temperature is between +2°C to -2.5°C of the setting temperature,
the compressor speed is controlled within the range shown in Table1.
However, the maximum speed is limited in the range shown in Fig. 1 based on the
fan speed mode and the outdoor temperature.
( Table 1 : Compressor speed range )
AO*G09LECAN
AO*G12LECAN
When the compressor operates for 30 minutes continuously at over the maximum speed ,
the maximum speed is changed from Maximum speed
( Fig. 1 : Limit of maximum speed based on outdoor temperature )
When outdoor
temperature drops
A zone
34°C
B zone
30°C
C zone
19°C
D zone
10°C
E zone
0°C
F zone
Minimum
Maximum
speed
speed
18rps
62rps
18rps
80rps
When outdoor
temperature rises
36°C
32°C
21°C
12°C
2°C
Maximum
speed
64rps
96rps
to Maximum speed .
Hi
09LECAN
A zone
64rps
B zone
64rps
C zone
64rps
D zone
42rps
E zone
52rps
F zone
52rps
A zone
96rps
12LECAN
B zone
96rps
C zone
96rps
D zone
57rps
E zone
57rps
F zone
57rps
01-01
Me
Lo
Quiet
50rps
42rps
30rps
50rps
42rps
30rps
50rps
42rps
30rps
35rps
30rps
23rps
45rps
40rps
29rps
45rps
40rps
29rps
61rps
51rps
33rps
61rps
51rps
33rps
61rps
51rps
33rps
42rps
36rps
27rps
42rps
36rps
27rps
42rps
36rps
27rps