Installation of Remote Controllers
Precautions
Low-voltage circuit provision is used for remote control communication, and as such, the remote
control cable is subject to the low-power circuit provision of internal wiring regulations and
!
therefore it cannot be brought into direct contact with a high-voltage AC power line, or housed in
the same conduit tube as a power line.
AI Models
Flush Wall Mounting
GB
The maximum extended length of the remote
control cable which can be used is 500 metres.
!
Install the remote controller where it can be easily
operated;
The decorative cover can be removed by prising
!
the section indicated by the arrow, using an
ordinary flat screwdriver;
The in-built memory backup capacitor will prevent
!
memory loss during power failure;
For details of setting the remote controller please
!
refer to the operating instructions in the Remote
Controller Owner's Manual.
Wall Surface Mounting
Make a U-shaped cut-out in the centre of the top edge of the decorative cover and pass the 3-core
!
PVC round cable through the cut out.
Wiring of two Remote Controllers
G
With the AI system the air conditioner can be controlled by two remote controllers the priority is
the last remote controller touched.
G
The remote controllers should be wired as shown in the diagram below:
1 Connect the remote controller terminals ABC together in parallel.
2 On the Sub remote controller set the dip SW1 switch 1 to the OFF position.
The total amount of cable between the indoor units and the remote controllers must not exceed 500m.
R
EMOTE
Cut-out
Indoor
Unit
ON
OFF
DIP
SW 1
ON Position 1:
Main Remote Controller
C
ONTROLLER
Mounting screws (x2) obtained locally
ON
OFF
OFF Position 1
Sub Remote Controller
~ 28 ~
3-core PVC cable,
obtained locally
Mounting screws (x2)
obtained locally