Unit Installation – MM-U Units
Check the dimensions of the unit illustrated in the
!
following figure. Use the accompanying template for
installation and adjust the position of the body of the
unit to the position of the opening on the ceiling.
Secure the cardboard template to the body of the
!
indoor unit with four bolts (M5 x 20mm).
Installing Ø 10 Hanging Bolts (4 pieces)
G
Install the hanging bolts at the intervals shown in the
following figure.
G
Use Ø 10 hanging bolts (to be locally procured).
Ceiling preparation: The actual procedure differs according
to the structure. Consult your builder or whoever was
responsible for the interior of the house/building.
(1) Removal of part of the ceiling plate:
In order to ensure that the ceiling is kept perfectly
horizontal and to prevent the ceiling from vibrating the
ceiling framework must be reinforced;
(2) Cut and remove part of the ceiling framework;
(3) Reinforce the ends of the ceiling framework where it was
cut and add framework to secure the ends.
G
Some piping and wiring connections must be made in
the ceiling after the unit has been suspended. After
selecting where the unit will be installed, decide on the
direction of the piping connection. If the ceiling is already
installed, prepare the refrigerant pipe, drain pipe, indoor
to outdoor unit connection wiring and the remote control
cord at the piping and wiring connection positions before
suspending the indoor unit.
MM-U056
MM-U080
Model (MM-)
U056
ØA
12.7
ØB
6.4
Fresh Air Inlet
620 (HANGER BOLT PITCH)
820 (EXTERNAL CASSETTE DIMENSION)
880 (CEILING OPENING)
940 (PANEL DIMENSION)
I
U
L
NDOOR
NIT
How to Install the Hanging Bolts
Installation on a newly installed concrete slab:
Use insert brackets or foundation bolts for the installation.
Knife-shaped
Installation on an existing concrete slab:
Use hole-in anchors, hole-in plugs
or hole-in bolts for the installation.
Installation on a steel frame:
Use the angular
bracket in the
structure or install
one for support.
Installation on a wooden structure:
Place a length of wood of the appropriate size across two
beams and install the hanging bolts into this length of wood.
U080
15.9
9.5
Drain pipe connection
(1'' BSP threaded connection)
~ 19 ~
OCATION
Sliding
bracket
bracket
(Foundation bolt for
hanging the piping)
Hanging
bolt
Cross
length
of wood
Hanging
bolt
Wiring connection (Gland
Plate 3 x Ø20 holes)
Drain Pipe
(1'' BSP Threaded Connection)
Reinforcing
bar
Foundation
bolt
Hanger bolt
Angular
bracket for
support
Beam
Ceiling
Refrigerant pipe
connection (Gas ØA)
Refrigerant pipe
connection (Liquid ØB)
GB