Case 4: Failure
H1P H2P H3P H4P H5P H6P H7P
x w w x x x x
(*) An error in the system interrupted the operation of the unit. Check the
error by using the error code displayed on the remote controller. For an
explanation of the error codes, see
on page 24
and solve the problem.
After correcting the problem, press
perform automatic refrigerant charging again starting from
step 4.2.
5
When charging is complete, determine the weight of refrigerant
that was added and fill in the amount in the "Additional
refrigerant charge label" attached to service precautions plate
on the unit.
6
After adding the refrigerant, do not forget to close the lid of the
service port. The tightening torque for the lid is 11.5~13.9 N•m.
V1
1
Service port for adding refrigerant
2
Liquid line stop valve
3
Gas line stop valve
4
Pipe fixing plate
Procedure 2: Charging while the outdoor unit is at a standstill
See
figure 6
for Sky Air or room air conditioner applications or
figure 7
for VRV applications.
1
Determine the weight of refrigerant to be charged additionally
referring to the item "Additional refrigerant charge" in
calculate the additional refrigerant to be charged" on page 12
Sky Air or room air conditioner applications or
the additional refrigerant to be charged" on page 13
applications, and fill in the amount in the "Additional refrigerant
charge label" attached to the unit.
2
After the vacuum drying is finished, open valve A and charge the
additional refrigerant in its liquid state through the liquid stop
valve service port taking into account following instructions:
-
Turn on the power of the outdoor unit and indoor units.
-
Check that gas and liquid stop valves are closed.
-
Stop the compressor and charge the specified weight of
refrigerant.
RXYSQ4~6P8V1B+Y1B
VRVIII-S System air conditioner
4PW68122-1 – 02.2011
Error code on remote
controller
See footnote
"Error codes on the remote controller"
button once and
BS1 MODE
1
Y1
2
3
"How to calculate
To avoid compressor breakdown. Do not charge the
refrigerant more than the specified amount.
If the total refrigerant cannot be charged while the
(*)
outdoor unit is at a standstill, it is possible to charge
the refrigerant by operating the outdoor unit using the
refrigerant charge function (refer to
on page
the outdoor unit is operating" on page
Procedure 3: Charging while the outdoor unit is operating
See the figure in
1
Close the front panel and turn on the power to all indoor units
and the outdoor unit.
2
Completely open the gas side stop valve and liquid side stop
valve. Valve A must be left fully closed.
3
Open valve A immediately after starting of the compressor.
4
Charge the additional refrigerant in its liquid state through the
service port of the liquid line stop valve.
5
While the unit is at a standstill and under setting mode 2 (refer to
"11.2. Checks before initial start-up" on page
mode" on page
refrigerant charging operation) to
starts. The blinking H2P led indicates test operation and the
remote controller indicates
(external control).
6
When the specified amount of refrigerant is charged, push the
BS3 RETURN
The operation automatically stops within 30 minutes.
4
If the refrigerant charge cannot be finished within 30 minutes,
repeat step 5.
2
If the operation stops immediately after restart, there is a
possibility that the system is overcharged.
3
The refrigerant cannot be charged more than this amount.
7
After the refrigerant charge hose is removed, make sure to close
valve A.
"How to
for
for VRV
23) and follow
"Procedure 3: Charging while
"How to connect the tank?" on page
22), set the required function A (additional
(ON). Then operation
ON
(test operation) and
button. Then operation stops.
"Setting mode 2"
17.
15.
22,
"Setting the
Installation manual
17