Connecting The Pv Array (Dc); Conditions For The Dc Connection - SMA SUNNY BOY 1600TL Installation Manual

Pv inverter
Hide thumbs Also See for SUNNY BOY 1600TL:
Table of Contents

Advertisement

SMA Solar Technology AG
5.4 Connecting the PV Array (DC)
5.4.1 Conditions for the DC Connection
Use of Adaptors
Adaptors (branch plug connectors) must not be visible or freely accessible in the immediate
surroundings of the inverter.
• The DC circuit may not be interrupted by adaptors.
• Observe the procedure for disconnecting the inverter as described in section
7.2 "Opening the Inverter" (page 38).
• Requirements for the PV modules of the connected strings:
– Same type
– Same number
– Identical alignment
– Identical tilt
• The connection cables of the PV modules must be equipped with connectors. You will find the
necessary DC connectors for DC connection included in the delivery.
• If the inverter is not equipped with an Electronic Solar Switch and the regulations in the country
of installation require an external DC switch-disconnector, install an external DC
switch-disconnector.
• The following limit values at the DC input of the inverter must not be exceeded:
Maximum input voltage
600 V (DC)
DANGER!
Risk of lethal electric shock or fire.
The maximum possible input current per string is limited by the connectors used. If the
connector is overloaded, an electric arc may occur and there is a risk of fire.
• Ensure that the input current for each string does not exceed the maximum flow
current of the connectors used.
Installation Guide
Maximum input current
11.0 A (DC)
SB16_21TL-IA-IEN112351
Electrical Connection
29