6.3.3 Additional Earthing of the Enclosure
If required in the country of installation, you can use the earth terminal on the enclosure to connect a
second protective conductor or as equipotential bonding.
1. Undo screw (A) half way. Use an Allen key (AF 4)
to do this.
2. Insert the stripped earthing cable (D) under the
clamping bracket (C) (maximum conductor cross-
section 10 mm²).
3. Fasten terminal (C):
– Place the conical spring washer over the screw.
The grooved side of the conical spring washer
must face towards the screw head.
– Tighten the screw (torque: 6 Nm). Use an Allen
key (AF 4) to do this.
☑ The teeth of the conical spring washer press into
the clamping bracket. The earthing cable now
has conductive connection to the enclosure.
6.4 Connecting the PV Array (DC)
6.4.1 Conditions for DC Connection
Use of Y adaptors
Y adaptors must not be visible or freely accessible within close proximity of the inverter.
• The DC circuit must not be interrupted by Y adaptors.
• Observe the procedure for disconnecting the inverter (see Section 8.2
"Disconnecting the Inverter from Voltage Sources" (page 56)).
• Requirements for
– same type
– same number of in-series-connected PV modules
– identical alignment
– identical tilt
• The connection cables of the PV modules must be equipped with connectors. The DC connectors
for the DC connection are included in the delivery.
• At the DC input of the inverter, the following limits must not be exceeded:
Maximum input voltage
Installation Manual
he PV modules of the connected strings:
t
750 V (DC)
Electrical Connection
Maximum input current
15.0 A (DC)