6  Electrical Connection

6.4 Connecting the PV Array (DC)

6.4.1 Conditions for DC Connection

The inverter has two input areas "A" and "B", each with its own MPP tracker. Two strings can be
connected to each of the two input areas.
A
A
Use of Y adaptors
Y adaptors must not be visible or freely accessible within close proximity of the inverter.
• The DC circuit must not be interrupted by Y adaptors.
• Observe the procedure for disconnecting the inverter from voltage sources
(see Section 9.2 "Disconnecting the Inverter from Voltage Sources", page 64).
• For each input area (A or B), the following requirements apply for the PV modules of the
connected strings:
– same type
– same number of in-series-connected PV modules
– identical alignment
– identical tilt
40
SB30-50TL-21-IA-en-21
B
SMA Solar Technology AG
Installation Manual