Appendix A. Diagnostic Info. & Hidden Menu Tables - Lennox ComfortSense L7742U Programming Manual

Touch screen
Hide thumbs Also See for ComfortSense L7742U:
Table of Contents

Advertisement

Appendix B. Diagnostic Information and Hidden Menu Tables
Diagnostic Information Table
Mes
sage
Type
Condition
Display Text (Screen1)
Error
AC power loss
with battery
(Battery Model
Only)
Error
AC power loss
without battery:
AC power loss
for greater than
250ms
Error
CPU memory
error
Note: If this Er-
ror occurs the
display goes
blank and all
relays are dis-
abled.
Error
ROM error
Note: If this Er-
ror occurs the
display goes
blank and all
relays are dis-
abled.
Error
Hi temperature
protection:
ambient temp.
exceeds 96F
(35.6C)
Error
Local Temp
Sensor error:
local temp sen-
sor reads out
of range −40F
to 158F
Error
EEPROM error
(Power ON)
Error
EEPROM error
(Operating)
506180−01 09/08
No message
No message
Not operate
Not operate
No message
TEMP SENSOR ERROR
CALL FOR SERVICE
MEMORY ERROR
CALL FOR SERVICE
MEMORY ERROR
CALL FOR SERVICE
Display Text
(Screen2)
Priority
Contact Info. Screen
0−Red
Alert
Contact Info. Screen
0−Red
Alert
Contact Info. Screen
0−Red
Alert
Page 20
Action to Clear /
System Action
Thermostat can detect
When AC power re-
AC power loss and Stat.
covers stat. can detect
will operate with batter-
and will operate on
ies.
AC.
Super Cap Or Lithium
When AC power (or
Battery will remember
battery power) is re-
the clock. All outputs
stored, normal opera-
will be off and O/B will
tion resumes.
remember the last state.
All stages of heat are
If temperature goes
turned off.
down, it will start work-
ing again.
Indoor temp is dis-
User have to call the
played as "EE" on the
number from contact
home screen. This will
information screen and
STOP all temperature
have someone come
related operation.
and replace the stat.
OR If the sensor read
back to with in the nor-
mal operating range,
the error message will
be cleared. Start work-
ing again.
System shall restore ev-
User shall call the
erything to Energy Star
dealer.
Default and operate. If
lithium Bat OR Super
Cap has Charge, it will
remember the previous
stored settings.
System shall operate in
User shall call the
normal mode operation
dealer.
until power off.
table continued on next page
Recovery
Condition

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents