Remote Control Unit - Samsung AJ009JNNDCH Service Manual

Multi air conditioner
Hide thumbs Also See for AJ009JNNDCH:
Table of Contents

Advertisement

7-1-2 Outoor Unit
1 Make sure that you install the outdoor unit in area not exposed to the rain or direct sun light.(Install a separate sunblind
if exposed to direct sun light.)
2 Make sure that you install the outdoor unit in area allowing the good air moment, not amplifying noise or vibration,
especialy to avoid disturbing neighbors. (Fix the unit firmly if it is mounted in a high place.)
3 Make sure that you install the outdoor unit in area providing the good ventilation and which is not dusty. It must not be
blocked by any obstacle affecting the airflow near the air inlet and the air outlet.
4 Make sure that you install the outdoor unit in area free from animals or plants.
5 Make sure that you install the outdoor unit in area not blocking the traffic.
6 Make sure that you install the outdoor unit in area easy to drain condensed water from the indoor unit.
7 Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable
length of a coolant pipe.
If you install within 50m, no add a additional refrigerent : This model is chargeless within 50m.
8 Make sure that you install the outdoor unit in an area which is large enough to accommodate the measurements
shown in figure on the next page.
If you install the excessive length of pipe, add additional refrigerant as 20g or 10g per unit meter; refer to the table
below.
Model
AJ020JCJ2CH
AJ024JCJ3CH
AJ036JCJ5CH

7-1-3 Remote Control Unit

1 Make sure that you use the remote control unit in an area free from obstacles such as curtains etc, which may block
signals from the remote control unit.
2 Make sure that you put the remote control unit in an area not exposed to direct sunlight, and where there is no source of
heat.
3 Make sure that you use the remote control unit in an area away from TVs, audio units, cordless phones, fluorescent
lighting fixtures and other electrical appliances (at least 1 meter).
7-2
Total connecting pipe length (L)
LT≤30m
LT>30m
LT≤40m
LT>40m
LT≤40m
LT>40m
Adding refrigerant
Chargeless
(LT- 30m)x10g
Chargeless
(LT- 40m)x10g
Chargeless
(LT- 40m)x20g