13-3. Address Setup

In case that addresses of the indoor units will be determined prior to piping work after cabling work
(Manual setting from remote controller)
<Address setup procedure>
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push
+
+
SET
for 4 seconds or more.
2
(← ← ← ← ← Line address) Using the temperature setup
/
buttons, set
3
Using timer time
4
Push
button. (OK when display goes on.)
SET
5
(← ← ← ← ← Indoor unit address) Using the temperature setup
/
buttons, set
6
Using timer time
7
Push
button. (OK when display goes on.)
SET
8
(← ← ← ← ← Group address) Using the temperature setup
/
buttons, set
9
Using timer time
0001
to Master unit, and
10
Push
button. (OK when display goes on.)
SET
11
Push
button.
Setup completes.
(The status returns to the usual stop status.)
3, 6, 9
1
<Operation procedure>
1
buttons simultaneously
12
to the item code.
/
buttons, set the line address.
13
to the item code.
/
buttons, set 1 to the line address.
14
to the item code.
0000
/
buttons, set
0002
to sub unit.
11
END
4, 7, 10
2
3
4
5
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Indoor unit address
to Individual,
For the above example, perform setting by connecting
singly the wired remote controller without remote
controller inter-unit cable.
Group address
Individual
Master unit : 0001
Sub unit
SET DATA
UNIT No.
R.C.
No.
UNIT
SET
CL
6
7
8
9
– 166 –
OUT
IN
2
Line address
1
1
1
2
Group address
1
: 0000
In case of group control
: 0002
2, 5, 8
10
11
END