Goodman *CVC96 Installation Instructions Manual page 39

Goodman *cvc96; *mvc96 two-stage gas furnace
Table of Contents

Advertisement

Example: Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air flow for the cooling system. Most cooling systems are designed to work with air flows between 350
and 450 CFM per ton. Most manufacturers recommend an air flow of about 400 CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
The cooling system manufacturer's instructions must be checked for required air flow. Any electronic air cleaners or other devices
may require specific air flows, consult installation instructions of those devices for requirements.
3. Knowing the furnace model, locate the high stage cooling air flow charts in the Specification Sheet applicable to your model.
Look up the cooling air flow determined in step 2 and find the required cooling speed and adjustment setting.
Example: A *M96VC0603B* furnace installed with a 2.5 ton air conditioning system. The air flow needed is 1000 CFM.
Looking at the cooling speed chart for *M96VC0603B*, find the air flow closest to 1000 CFM. A cooling airflow of
1007 CFM can be attained by setting the cooling speed to "C".
5. Locate the blower speed selection DIP (S3) switches on the integrated control module. Select the desired "cooling" speed tap
by positioning switches 1 and 2 appropriately. Select the desired "adjust" tap by positioning switches 3 and 4 appropriately. To
enable adjustments and select -5, 5, -10 or 10% trim, you must set dip switch S5-2 to ON. If S5-2 is in the OFF position
, you will receive 0% trim. Refer to the following figure for switch positions and their corresponding taps. Verify CFM by
noting the number displayed on the dual 7-segment LED display.
6. The multi-speed circulator blower also offers several custom ON/OFF ramping profiles. These profiles may be used to enhance
cooling performance and increase comfort level. The ramping profiles are selected using DIP
switches S4- 1, 2. Refer to the following figure for switch positions and their corresponding
taps. Refer to the following bullet points for a description of each ramping profile. Verify
CFM by noting the number displayed on the dual 7-segment LED display.
Profile A
provides only an OFF delay of one (1) minute at 100% of the cooling demand airflow.
OFF
Profile B
ramps up to full cooling demand airflow by first stepping up to 50% of the full
demand for 30 seconds. The motor then ramps to 100% of the required airflow. A one (1)
minute OFF delay at 100% of the cooling airflow is provided.
50% CFM
OFF
1/2 min
Profile C
ramps up to 85% of the full cooling demand airflow and operates there for
approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile C
also has a one (1) minute 100% OFF delay.
OFF
100% CFM
100% CFM
Figure 49
100% CFM
100% CFM
Figure 50
100% CFM
Figure 51
39
Sw itch Bank: S4
DIP Sw itch No.
Ramping
Prof iles
1
A*
OFF
B
ON
C
OFF
D
ON
(*Indicates factory setting)
OFF
1 min
OFF
1 min
OFF
2
OFF
OFF
ON
ON

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

*mvc96

Table of Contents