Goodman *CVC96 Installation Instructions Manual page 21

Goodman *cvc96; *mvc96 two-stage gas furnace
Table of Contents

Advertisement

4. Remove the two plugs from the right side of the
cabinet and install them in the blower deck.
5. (Draining the Vent Elbow ) Locate hose #5 and
cut it at line "C". Install the cut end of hose #5
from outside the cabinet through the cabinet
drain hole nearest the top. Secure it to the barbed
fitting in the elbow with a red clamp.
6. (Draining the Collector Box) Install the non-
grommet end of hose #11 from outside the
cabinet in the bottom drain hole. Install on
collector box and secure with a silver clamp.
7. Use two silver clamps and secure the hoses to
drain trap. The trap outlet faces the front of the
furnace. Secure the trap to the cabinet using two
screws removed in step 2 by inserting the two
screws through the large set of holes in the top
mounting tabs of the trap into the two predrilled
holes in the side of the cabinet.
8. Refer to Field Supplied Drain section for
instructions on field supplied / installed drain on outlet of furnace trap.
U
PFLOW MODEL INSTALLED HORIZONTALLY WITH LEFT SIDE DOWN
Minimum 5 ½" clearance is required for the drain trap beneath the furnace.
*Also see Front Cover Pressure Switch Tube Location on page 10
1. Remove the clamps from the two drain tubes on the trap.
2. Remove the two screws holding the drain trap to the blower deck.
3. Remove the trap and hoses from the blower deck .
4. Remove the two plugs from the left side of the cabinet and install them in the blower deck.
5. (Draining the Vent Elbow) Locate hose #6. Measuring from the non-grommet end; cut off and discard 1 ½" for a "D"
width cabinet, 5" for a "C" width cabinet, 8 ½" for a "B" width cabinet.
6. Remove the rubber plug from vent – drain elbow side
port. Place hose #6 on the vent – drain elbow side port
and secure with a silver clamp .
7. Place cap on vent – drain elbow barb fitting and
secure with red clamp
8. Locate hose #5 and cut 3" from the non-grommet end.
Discard the section without the grommet.
9. Insert the cut end of tube #5 through the lower cabinet
drain hole.
10. Connect hose #6 & hose #5 using 100º elbow and
secure with two red clamps
11. (Draining the Collector Box) Install the non-grommet
end of hose #11 from outside the cabinet in the bottom
drain hole. Install on collector box and secure with a
silver clamp.
12. Use two silver clamps and secure the hoses to drain
trap. The trap outlet faces the front of the furnace.
Secure the trap to the cabinet using two screws
removed in step 2 by inserting the two screws through
the large set of holes in the top mounting tabs of the trap into the two predrilled holes in the side of the cabinet.
13. Place cap on vent – drain elbow barb fitting and secure with red clamp.
14. Refer to Field Supplied Drain section for instructions on field supplied / installed drain on outlet of furnace trap.
Hose #11
Hose #6
Hose #11
Hose #5
21
Hose #5-Cut at "C"
Figure 23
Figure 24