Angled Wall Radiation Shield; Chimney Support Installation; Chimney Chase And Multiple Terminations - Lennox Hearth Products MONTECITO ESTATE MONTEST Installation And Operating Instructions Manual

Epa wood-burning fireplace signature collection
Table of Contents

Advertisement

ANGLED WALL RADIATION SHIELD

(XRSMI30 and AC10RSMI30)
When traversing a combustible wall with the chimney at a 30º or 45º
angle, an angled fi restop or wall radiation shield must be installed. Only
one is required.
Note: 45º angle for Canada only (XRSMI45).
In cold climate locations (climates where temperatures will fall below 32º
F / 0º C), we recommend that you use the insulated wall radiation shield
since it will maintain the home's thermal barrier.
XRSMI30 and AC10RSMI30
(XRSMI45 - Canada Only)
Chimney Model (7" dia).
Secure Temp™ S2100+
Nova Temp™ HT6000+
Secure Temp GX
(US only)
Secure Temp S2100+
Nova Temp HT6000+
ACBI
Table 5
Insulated Wall
Drywall
Figure 30

CHIMNEY SUPPORT INSTALLATION

Universal Roof Support
This support has three possible uses:
1. For Secure Temp S2100+ / Nova Temp HT6000+ / Secure Temp GX, it
must be used on a roof to support the chimney.
2. It may be used on a fl oor, ceiling or roof above an offset to support
the chimney above the offset.
3. It may be used on a fl oor, ceiling or roof as a supplementary support
when the chimney height exceeds 15 feet (4.6 m).
Table 6 gives maximum height of supported chimney.
NOTE: For the ACBI chimney, a support section (ACBI7SL) must be used
every 30 feet (9m) or an universal support every 20 feet (6m) instead of
the universal roof support (ST).
18
Angle
Hole Size
15" x 38-1/4"
30º
(380 mm x 972 mm)
45º
15" x 25-7/8"
Canada only
(380 mm x 657 mm)
17 x 42-1/2"
30º
(432 mm x 1080 mm)
Insulated Wall
Radiation Shield
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
For roof support installation, refer to the instructions provided with the
support.
Universal Offset Support
This support is used to support the chimney above an offset. When
the chimney offset is used to traverse a wall this support may be used
on the wall to support the chimney. The maximum heights are given in
Table 6. For offset support installation, refer to the instructions provided
with the support.
CHIMNEY
7" Diameter
Secure Temp S2100+
Nova Temp HT6000+
Secure Temp GX
ACBI
Table 6

CHIMNEY CHASE AND MULTIPLE TERMINATIONS

For the purpose of this manual, a chimney chase is considered a part of
the chimney system rather than part of a building. The termination must
be placed a minimum of 18" (460 mm) above the chase.
For installations where more than one chimney is located in the same
chase or within the same area, we suggest that their terminations be
separated by at least 16" (410 mm) horizontally, and 18" (460 mm) verti-
cally. This separation is to prevent smoke migrating from one chimney
to another (see Figure 31).
18" (460 mm)
16" (410 mm)
Figure 31
MAXIMUM HEIGHT OF
SUPPORTED CHIMNEY
Offset Support
Roof Support
16 feet (5.49 m).
18 feet (6.1 m).
40 feet (12.19 m).
50 feet (15.20 m).
18" (460 mm)
18" (460 mm)
16" (410 mm)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents