Grant EUROFLAME 50/70 User, Installation And Servicing Instructions page 14

Grant euroflame kitchen/utility and boiler house models 50/70, 70/90, 90/120 and kitchen/utility system models 50/90, 90/120
Table of Contents

Advertisement

3.4.5 Tiger Loop system - (See Figs. 4 and 5)
1 When The storage tank is below the burner, an
alternative to a two pipe system can be achieved using
the Tiger Loop oil deaerator. This effectively removes
the air from the oil supply on a single pipe lift.
2 The Tiger Loop is connected close to the boiler as
a two pipe system (omitting the non-return valve)
as shown in Fig. 4. Refer to the manufacturers
instructions supplied with the Tiger Loop.
The Tiger Loop must be mounted vertically.
Note: To prevent any possibility of fuel fumes
entering the building, the Tiger Loop must be
fitted outside.
14
3 - GENERAL BOILER INFORMATION
Fig. 4 - Tiger loop system
Tiger Loop
RETURN
FROM PUMP
SUPPLY
TO PUMP
Fig. 5 - Tiger loop
Euroflame Oil Boilers
3 To be used with a Tiger Loop system, the burner
must be fitted with an additional flexible fuel line
(a flexible fuel line (900 mm) and
male adaptor are available from Grant Engineering
(UK) Limited). See section 3.4.6.
1/4" BSP female
connections
SUPPLY
FROM TANK
3
1
/
" to
/
" BSP
8
4