Fuel supply
3.4
3.4.1 Fuel storage
A painted (outside only) storage tank must be
constructed to BS 799:5:1987 and should include the
following:-
a A fuel level gauge (not a glass type).
b A vent pipe incorporating a weatherproof
termination (bend or cap) of a diameter not less
than the filling pipe.
c A sludge valve.
d An outlet valve at the opposite end of the tank
to the sludge valve.
The tank should be positioned in accordance with the
recommendations given in BS 5410:1:1997, which
gives details of filling, maintenance and protection
from fire.
The tank should be suitably supported so as to obtain a
slope of 20 mm per metre towards the sludge valve.
A galvanised tank must not be used.
A plastic tank may be used and must comply with OFS
T100.
Note: Plastic tanks should be adequately and
uniformly supported on a smooth level surface, across
their entire base area.
3.4.2 Fuel pipes
1 Fuel supply pipes should be of copper tubing with
an internal diameter of at least 8 mm.
Soldered joints should not be used.
Galvanised pipe must not be used.
2 Flexible pipes must not be used outside the boiler case.
3 A remote sensing fire valve must be installed in the
fuel supply line (outside) where it enters the
building, with the sensing head located above the
burner. Recommendations are given in BS
5410:1:1997.
4 A metal bowl type filter with a replaceable
micronic filter must be fitted in the fuel supply line
adjacent to the boiler. A shut-off valve should be
fitted before the filter, to allow the filter to be
serviced.
5 A flexible fuel line, adaptor and
valve are supplied loose with the boiler for the final
connection to the burner. If a two pipe system or Tiger
Loop system is used, an additional flexible fuel line
3
(900 mm) and
/
" to
8
available from Grant Engineering (UK) Limited.
12
3 - GENERAL BOILER INFORMATION
1
/
" BSP isolation
4
1
/
" BSP male adaptor are
4
Euroflame Oil Boilers
6 Flexible fuel lines should be inspected annually
when the boiler is serviced and replaced every two
years.
7 The use of a 'Tankmaster' and Tiger Loop is an
ideal way of delivering an oil supply to the boiler.
The Tankmaster unit, fitted to the storage tank,
includes a filter, sight tube, shut-off valve and fire
valve. A separate fire valve is required in the fuel
line (outside) where it enters the building
containing the boiler. See Fig. 4.
3.4.3 Single pipe system - (See Fig. 2)
1 Where the storage tank outlet is above the burner
the single pipe system should be used. The height
of the tank above the burner limits the length of
pipe run from the tank to the burner.
2 As supplied the burner is suitable for a single pipe
system.
3.4.4 Two pipe system - (See Fig. 3)
1 When the storage tank outlet is below the burner,
the two pipe system should be used. The pipe runs
should be as shown in Fig. 3. The return pipe
should be at the same level in the tank as the
supply pipe, both being 75 to 100 mm above the
base of the tank. The pipe ends should be a
sufficient distance apart so as to prevent any
sediment disturbed by the return entering the
supply pipe.
2 Avoid the bottom of the tank being more than 3 m
below the burner.
3 A non-return valve should be fitted in the supply
pipe together with the filter and fire valve. The
return pipe must be unrestricted.
4 To be used with a two-pipe system, the burner
must be fitted with an additional flexible fuel line
(a flexible fuel line (900 mm) and
male adaptor are available from Grant Engineering
(UK) Limited). See section 3.4.6.
5 The pump vacuum should not exceed 0.4 bar.
Beyond this limit gas is released from the oil.
For guidance on installation of top outlet fuel tanks and
suction oil supply sizing, see OFTEC booklet T1/139.
Available at www.oftec.org.uk
3
1
/
" to
/
" BSP
8
4