Selection of the place and installation of the equipment
The indoor unit is designed for suspension on the wall using a mounting desk. It has to be placed in the room in
a way that enables the access for service and maintenance (see the illustration under).
The outdoor unit is designed to be attached to a stand. The stand is necessary for an appropriate evaporator
defrosting. This stand must be firmly fastened to a concrete base large enough to prevent the unit from toppling
over in windy weather. Its position must be chosen with sufficient space for free airflow to the evaporator and
for easy service access.
When installing the outdoor unit in a dense urban area, make sure to observe the noise regulation standards. In
this case, a noise test might be necessary.
O.U. environment according to Czech Standard ÈSN 33 2000-3
I.U. environment according to Czech Standard ÈSN 33 2000-3
50 cm
65 cm
Connection of the refrigerant circuit
Do not exceed the maximum length of the connection piping. Failing to do this, the capacity
parameters cannot be ensured and there is a risk of equipment damage.
Model
Mini 5
Mini 8,11,14,16(HP)
* See the technical data for the relevant outdoor unit.
It is necessary to insulate the piping sufficiently.
Use insulation suitable for refrigerant circuits. The temperature on the piping surface can
reach up to 120°C! For outdoor installation, the minimum insulation thickness should be
20 mm. For indoor installation, insulation thickness of 10-15 mm is sufficient.
The above mentioned parameters are valid for insulation that comply with thermal
resistance of 0,45W(m.K) or better (at 20°C).
65 cm
min. 30 cm
Dimension*
Fluid
Gas
6 mm
12 mm
10 mm
16 mm
AA2-AA5; AB7; AD3
AA5; AB5
Length*
Max. high
difference*
Min.
Max.
2,5 m
25 m
15 m
2,5 m
30 m
20 m