Impromat Klima ATW-MINI Technical Manual page 10

Air to water heat pump atw-mini
Table of Contents

Advertisement

10.2.2 Parameters settings
The menu with a number of parameters that can be viewed, and modified, if necessary. The current value of the
parameter is displayed. If the parameter is user-editable, a box labelled „New” is displayed.
Current value
New value
(select to edit)
Current value
Edited value
Parameters that cannot be edited:
- Mode V2
- Maximum temperature of the refrigerant in the heating mode
- Minimum temperature of the refrigerant in the cooling mode
- Mode V1
Editable parameters:
- Time limit - supply water - time during which the HDW tank will be heated.
- Temperature reduction - cooling - how many degrees will the temperature increase during cooling.
- Temperature reduction - heating - how many degrees will the temperature decrease during heating.
- Bivalent temperature - outdoor temperature that causes the outdoor unit shutdown.
- Cooling water temperature - requied water temperature in the cooling mode.
- Power limit - cooling - maximum capacity of the outdoor unit during cooling mode.
- Power limit - heating - maximum capacity of the outdoor unit during heating mode.
- Max. temperature - supply water - maximum temperature in the HDW tank.
- Min. temperature - supply water - minimum temperature in the HDW tank.
- Power limit - supply water - maximum capacity of the outdoor unit during HDW heating.
- Heating water (outdoor +20°) - required heating water temperature at +20°C outdoor temp.
- Heating water (outdoor +12°) - required heating water temperature at +12°C outdoor temp.
- Heating water (outdoor +4°) - required heating water temperature at +4°C outdoor temp.
- Heating water (outdoor -4°) - required heating water temperature at -4°C outdoor temp.
- Heating water (outdoor -12°) - required heating water temperature at -12°C outdoor temp.
- Heating water (outdoor -20°) - required heating water temperature at -20°C outdoor temp.
- Regulation constant - value affecting the communication speed with the outdoor unit.
- Indoor temperature limit - heating - maximum indoor temperature in the heating mode.
- Indoor temperature limit - cooling - minimální indoor temperature in the cooling mode.