Removal Of Fan Rotor / Fan Motor - Daikin FWXV15AVEB Service Manual

Fan coil unit - convector - floor standing type a-series
Hide thumbs Also See for FWXV15AVEB:
Table of Contents

Advertisement

SiBE611027_A
1.9

Removal of Fan Rotor / Fan Motor

Procedure
Step
1. Remove the fan rotor.
1
Remove the 4 screws
and remove the
bellmouth.
2
Remove the nut and
remove the fan rotor.
2. Remove the fan motor.
1
Release the harness of
the fan motor from the
hook.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Bellmouth
Nut
Fan rotor
(R12503)
(R12504)
Hook
(R12443)
Indoor Unit
Points
The screw has reverse
winding.
Nut size: M6
10 mm
(R12236)
When reassembling, align
mark of the indoor fan
with D-cut section of the
motor shaft.