data plate and verify that liquid supercooling at the thermostatic intake is 3 to 5°C less than the condensation
temperature on the manometer scale and that the superheating is between 4 and 7°C
NOTE: when charging with R407C check the liquid supercooling value (3 to 5°C) and not the sight glass.
Check the type of refrigerant used on the unit data plate and on the compressor data plate.
If it is necessary to top up the oil, use only the oils listed below:
R22 (Mineral oil)
R407C (POE)
Do not use the compressor to create a vacuum in the system.
When charging the unit, use refrigerant in the liquid state.
IMPORTANT WARNINGS
Refrigerant
Maneurop 160P - Mineral / ISO 32
Maneurop 160SZ
Recommended oil