Uniflair Aquaflair 00182 Instruction Manual page 19

Table of Contents

Advertisement

(see also the enclosed installation drawings and hydraulic diagram)
1) CHECK that the section of the chilled water pipes and the power of the circulation pump fitted are
sufficient. An inadequate water flow significantly reduces the cooling capacity of the unit.
2) CHECK the water intake/output directions. There are labels next to the intake, output and heat recovery
connections as shown in the diagram below. The bleed (S) and drain (V) valves are part of the special input
and output connections.
ARA
Water Intake
Ø 2" GAS F.
00152
Ø 2" GAS F.
00182
00202
Ø 2" GAS F.
00232
Ø 2" GAS F.
00252
Ø 2" GAS F.
00302
Ø 2" GAS F.
00403
Ø 2" GAS F.
00504
Ø 2" GAS F.
3) CONNECT the chiller using flexible tubes to stop the transmission of vibrations. Fit shut-off valves so that
the unit can be isolated from the water circuit;
4) INSULATE the chilled water pipes to stop the formation of condensation;
5) FIT temperature measuring points on the pipes near the intake and output connections;
6) INSTALL a metal filter in the section of pipe next to the unit intake to prevent pieces of welding or flakes of
rust entering the heat exchanger.
7) PROVIDE a discharge well near the output connection in case the unit needs to be emptied.
HYDRAULIC CONNECTIONS
INGRESSO - INLET
EINGANG - ENTREE
I
ENTRADA
ev
USCITA - OUTLET
AUSGANG - SORTIE
U
SALIDA
ev
Water Output
Ø 2" GAS F.
Ø 2" GAS F.
Ø 2" GAS F.
Ø 2" GAS F.
Ø 2" GAS F.
Ø 2" GAS F.
Ø 2" GAS F.
Ø 2" GAS F.
S
INTAKE
CONNECTION
OUTPUT
CONNECTION
Heat recovery intake
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
19
V
Heat recovery output
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.
Ø 1 1/4" GAS F.