Setting The Safety Devices - Uniflair Aquaflair 00182 Instruction Manual

Table of Contents

Advertisement

The function parameter values set on the microprocessor control are given in the enclosed instruction
manual. The table below gives the settings of the safety devices; these are also on the data plate on the unit.
Component
Refrigerant circuit (R22 – R407C)
High pressure pressostat (AP1-AP2)
Low pressure pressostat (BP1-BP2)
Anti-freeze protection
Refrigerant safety valve (VSA1-VSA2) -
Models 0152...0302
Refrigerant safety valve (VSA1-VSA2) -
Models 0403...0504
Water circuit
2
Flow gauge
Water side safety valve
1
Values refer to standard version with pure water.
2
With optional pump group.
Setting of safety devices.

SETTING THE SAFETY DEVICES

1
1
Setting
Differential
27.5 bar
2.6 bar
4 °C
32.0 bar
28.0 bar
105 mbar
80 mbar
3.0 bar
32
Re-set
--
manual
1.4 bar
4.0 bar
4 °C
--
--
--
--