Fz4B Low Temperature Zone Card - Ferroli ECONCEPT SOLAR ST Instructions For Use, Installation And Maintenance

Table of Contents

Advertisement

ECONCEPT SOLAR ST

4.8 FZ4B low temperature zone card

Service Menu
Press the Ok button for 5 seconds to access the zone controller Service Menu.
Press the buttons
"tS" = Transparent Parameters Menu
"In" = Information Menu
"Hi" = History Menu (of the zone controller)
"rE" = History Menu Reset (of the zone controller).
After selecting the Menu, press the Ok button to access it.
"tS" - Transparent Parameters Menu
The zone controller is provided with 35 transparent parameters also modifiable from Remote Control (Service Menu):
Remote
Zone Card
Control
FZ4B
01
P01
02
P02
03
P03
04
P04
05
P05
06
P06
07
P07
08
P08
09
P09
10
P10
11
P11
12
P12
13
P13
14
P14
15
P15
16
P16
17
P17
18
P18
19
P19
20
P20
21
P21
22
P22
23
P23
24
P24
25
P25
26
P26
27
P27
28
P28
29
P29
30
P30
31
P31
32
P32
33
P33
34
P34
35
P35
Press the "+" and "-" buttons to scroll the list of parameters in increasing or decreasing order respectively. To modify
the value of a parameter, press the Ok button after selecting it: press the + and - buttons to modify it, and the setting
will be automatically saved. Press the Ok button to return to the list of parameters. Press the Ok button for 3 seconds
to return to the Service Menu. Press the Ok button for 5 seconds to exit the Service Menu.
EN
and
to select:
Boiler Card
Description
(if prearranged)
transparent parameters
Zone1 Min. Temperature
Zone1 Max. Temperature
Zone1 calculated set point offset
Do not modify
o01
Zone1 External Probe Curve
o02
Zone1 External Probe Offset
Zone2 Min. Temperature
Zone2 Max. Temperature
Zone2 calculated set point offset
DO NOT MODIFY
o03
Zone2 External Probe Curve
o04
Zone2 External Probe Offset
Zone3 Min. Temperature
Zone3 Max. Temperature
Zone3 calculated set point offset
DO NOT MODIFY
o05
Zone3 External Probe Curve
o06
Zone3 External Probe Offset
Mixing valve on+off time
Mixing valve boost
Mixing valve on time for °C
DO NOT MODIFY
DO NOT MODIFY
DO NOT MODIFY
DO NOT MODIFY
DO NOT MODIFY
Post-circulation time
DO NOT MODIFY
Delay for Zone
DO NOT MODIFY
DO NOT MODIFY
DO NOT MODIFY
DO NOT MODIFY
DO NOT MODIFY
DO NOT MODIFY
cod. -- - 11/2010 (Rev. 00)
Default
Recom-
Range
(for mixed
mended for
zone)
Direct Zone
10-90°C
10°C
10-90°C
40°C
0-40°C
10°C
10-90°C
90°C
0-10
0
20-40°C
30°C
10-90°C
10°C
10-90°C
80°C
0-40°C
0°C
10-90°C
90°C
0-10
0
20-40°C
30°C
10-90°C
10°C
10-90°C
80°C
0-40°C
0°C
10-90°C
90°C
0-10
0
20-40°C
30°C
0-15sec
15sec
0-120sec
0sec
0-15sec/°C
1sec/°C
0-20°C
4°C
70-85°C
80°C
0-60°C
0°C
0-1
0
10-65°
55°C
0-20 min
10 min
0-1
0
0-255 sec.
30 sec.
0-1
0
0-3 min
3 min
0-10°C
5°C
0-10 min
2 min
0-1
0
0-1
0
10°C
70÷80°C
0°C
47