2.7 Condensate drain connection

The boiler is equipped with an internal trap to drain condensate. Fit the inspection union A and flexible tube B, pressing
it in for approx. 3 cm and securing it with a clamp. Fill the trap with approx. 0.5 l. of water and connect the flexible tube
to the drainage system.
fig. 25
20
EN
cod. -- - 11/2010 (Rev. 00)