ECONCEPT SOLAR ST
References for Compensation curve and curve offset
If the room temperature is lower than the required value, it is advisable to set a higher order curve and vice versa. Pro-
ceed by increasing or decreasing in steps of one and check the result in the room.
OFFSET = 20
90
10
85
80
70
60
50
40
30
20
20
10
Adjustments from remote timer control (for Low Temperature Zone only)
A
If the Remote Timer Control (optional) is connected to the boiler, the above adjustments are managed accord-
ing to that given in table 1. Also, the control panel display (detail 5 - fig. 1) shows the actual room temperature
read by the Remote Timer Control.
Table. 1
DHW temperature adjustment
Eco/Comfort selection
EN
90
10
85
80
70
60
50
40
30
20
20
10
fig. 13 - Compensation curves
9
8
7
6
5
4
3
2
1
0
-10
-20
fig. 14 - Example of parallel compensation curve shift
Adjustment can be made from the Remote Timer Control menu and the boiler
control panel.
On disabling DHW from the Remote Timer Control menu, the boiler selects
the Economy mode. In this condition, the ECONOMY/COMFORT button
(detail 7 - fig. 1) on the boiler panel is disabled .
On enabling DHW from the Remote Timer Control menu, the boiler selects
the Comfort mode. In this condition , one of the two modes can be selected
with the ECONOMY/COMFORT button (detail 7 - fig. 1) on the boiler panel .
cod. -- - 11/2010 (Rev. 00)
9
8
7
6
5
4
3
2
1
0
-10
-20
OFFSET = 40
90
10
85
80
70
60
50
40
30
20
20
10
9
8
7
6
5
4
3
2
1
0
-10
-20
11

Advertisement

Table of Contents
loading

Table of Contents