Centralized Controller - Samsung BACnet Gateway MIM-B17N Installation Manual

Hide thumbs Also See for BACnet Gateway MIM-B17N:
Table of Contents

Advertisement

ERV
Single ERV unit has following point list.
Instance
Object
Number
1
Power On/Off operation
2
Filter sign status
3
Filter sign reset
4
Operation mode status
5
Fan speed status
6
Remote controller limit status
Integrated error code of ERV
7
unit
8
ERV Notify
SIM
Single SIM has following point list.
Instance
Object
Number
1
SIM error code
2
SIM Notify

Centralized controller

Single Centralized controller has following point list.
Instance
Object
Number
Centralized controller
1
error code
Centralized controller
2
notify
Interface module
Single Interface module has following point list.
Instance
Object
Number
1
Outside temperature
* 2
Cool capacity compensation
* 3
Heat capacity compensation
4
Compressor status
5
Interface module error code
6
Interface module notify
(*) Mark is optionally supported.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 65
Object
Object Name
Type
BV
ERV_Power_xx_xxxxxx
BI
ERV_FilterSign_xx_xxxxxx
BO
ERV_FilterSign_Reset_xx_xxxxxx
MV ERV_Operation_Mode_xx_
xxxxxx
MV ERV_FanSpeed_xx_xxxxxx
MV ERV_Remocon_Limit_xx_xxxxxx Enable
AI
ERV_Error_Code_xx_xxxxxx
NC
ERV_Notify_xx_xxxxxx
Object
Object Name
Type
AI
SIM_Error_Code_xx_xx
NC
SIM_Notify_xx_xx
Object
Object Name
Type
AI
Central_Error_Code_xx_xx
NC
Central_Notify_xx_xx
Object
Object Name
Type
AI
ODU_Outside_Temp_xx_xxxx
ODU_Cool_Compensation_xx_
AV
xxxx
ODU_Heat_Compensation_xx_
AV
xxxx
BI
ODU_Comp_Status_xx_xxxx
AI
Repeater_Error_Code_xx_xxxx
IM_Notify_xx_xxxx
NC
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3 Text-4 Text-5
Off
On
False
True
False
True
Auto HeatEx Bypass Sleep
Low
High
Turbo
Disable
Conditional
RC
RC
RC
Refer to list of error code
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Status value
Refer to list of error code
When the error occurred, send event
to list of destination in the recipient_
list. (Max : 8)
Status value
Refer to the list of the integrated
error code
When the error occurred, send
event to list of destination in the
recipient_list. (Max : 8)
Unit
Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
°C
0 : 5~7°C / 1 : 7~9°C / 2 : 9~11°C /
3 : 10~12°C / 4 : 11~13°C / 5 : 12~14°C /
6 : 13~15°C / 14 : Auto control (from ODU)
0 : 25kg/cm² / 1 : 26kg/cm² /
2 : 27kg/cm² / 3 : 28kg/cm² /
4 : 29kg/cm² / 5 : 30kg/cm² /
6 : 31kg/cm² / 7 : 32kg/cm² /
8 : 33kg/cm² / 14 : Auto control (from ODU)
False
True
Refer to the list of the integrated error code
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
65
E-