AHU Kit
Single AHU unit has following point list.
Instance
Object
Number
1
Indoor Temperature
2
Set temperature
Setting lower temperature
3
limit
Setting upper temperature
4
limit
The power value of an indoor
5
unit after the basic date
The number of hours usage of
6
an indoor unit after the basic
date
7
Power value within period
The number of hours usage of
8
an indoor unit within period
9
Power On/Off
Applying lower temperature
10
limit setting
Applying upper temperature
11
limit setting
12
Filter sign status
13
Filter sign reset
14
Operation mode status
15
Operation mode limit status
16
Remote controller limit status
Integrated error code of both
17
indoor unit and outdoor unit
Discharge cooling set
* 18
temperature
Discharge heating set
* 19
temperature
Discharge current
* 20
temperature
* 21
Humidification setting
* 22
Outdoor air intake setting
* 23
Outdoor cooling setting
* 24
Fan speed status
* 25
Set humidity status
* 26
Current humidity status
27
AHU Notify
(*) Mark is optionally supported.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 63
Object
Object Name
Type
AI
AHU_RoomTemp_xx_xxxxxx
AV
AHU_Temp_Set_xx_xxxxxx
AHU_Cool_LimitTemp_xx_
AV
xxxxxx
AHU_Heat_LimitTemp_xx_
AV
xxxxxx
AHU_Baseline_kWh_xx_
AI
xxxxxx
AHU_Baseline_Minute_xx_
AI
xxxxxx
AHU_Period_kWh_xx_
AI
xxxxxx
AHU_Period_Minute_xx_
AI
xxxxxx
BV
AHU_Power_xx_xxxxxx
AHU_Cool_Limit_set_xx_
BV
xxxxxx
AHU_Heat_Limit_set_xx_
BV
xxxxxx
BI
AHU_FilterSign_xx_xxxxxx
AHU_FilterSign_Reset_xx_
BO
xxxxxx
MV AHU_Operation_Mode_xx_
xxxxxx
AHU_Mode_Limit_xx_
MV
xxxxxx
MV AHU_Remocon_Limit_xx_
xxxxxx
AI
AHU_Error_Code_xx_xxxxxx
AHU_DisCoolSetTemp_xx_
AV
xxxxxx
AHU_DisHeatSetTemp_xx_
AV
xxxxxx
AHU_Dis_CurrentTemp_xx_
AI
xxxxxx
AHU_Humidification_xx_
BV
xxxxxx
BV
AHU_OAIntake_xx_xxxxxx
AHU_OutdoorCool_xx_
BV
xxxxxx
MV AHU_FanSpeed_xx_xxxxxx
MV AHU_SetHumidity_xx_
xxxxxx
AHU_CurrentHumidity_xx_
MI
xxxxxx
NC
AHU_Notify_xx_xxxxxx
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3 Text-4 Text-5
°C
°C
°C
°C
kWh
Minute
kWh
Minute
Off
On
False
True
False
True
False
True
False
True
Auto
Cool
Heat
Fan
No
Cool
Heat
Limit
Only
Only
Enable
Disable
Conditional
RC
RC
RC
Refer to list of error code
°C
°C
°C
Off
On
Off
On
Off
On
Low
Mid
High
Low
Mid
High
Low
Mid
High
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Dry
63
E-
2013-04-25 오전 10:14:42