BACnet Point List (Continued)
EHS
Single EHS Unit has following point list.
Instance
Number
1
Room temperature
2
Set temperature
3
Set temperature of water out
4
Set temperature of hot water
5
Setting lower temperature limit
6
Setting upper temperature limit
7
Lower temperature limit for water out
8
Upper temperature limit for water out
9
Upper temperature limit for hot water
10
The power value after the basic date
The number of hours usage of an
11
indoor unit after the basic date
12
Power value within period
The number of hours usage of an
13
indoor unit within period
14
Current temperature of water out
15
Current temperature of hot water
16
Displayed temperature type
17
Thermostat usage
18
Outing
19
Power On/Off
20
Setting lower temperature limit
21
Setting upper temperature limit
Apply lower temperature limit for
22
water out
Apply upper temperature limit for
23
water out
24
Apply upper temperature limit for hot water
25
On/Off status of hot water mode
26
Status of quiet operation
27
Operation mode status
28
Operation mode limit status
29
Remote controller limit status
30
Status of hot water operation mode
Integrated error code of both indoor
31
unit and outdoor unit
32
EHS notifiy
64
E-
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 64
Object
Object
Type
AI
EHS_RoomTemp_xx_xxxxxx
AV
EHS_Temp_Set_xx_xxxxxx
AV
EHS_WaterOutTemp_Set_xx_xxxxxx
AV
EHS_HotWaterTemp_Set_xx_xxxxxx
AV
EHS_Cool_LimitTemp_xx_xxxxxx
AV
EHS_Heat_LimitTemp_xx_xxxxxx
AV
EHS_WOCoolLimitTemp_xx_xxxxxx
AV
EHS_WOHeatLimitTemp_xx_xxxxxx
AV
EHS_WTHeatlLimitTemp_xx_xxxxxx
AI
EHS_Baseline_kWh_xx_xxxxxx
AI
EHS_Baseline_Minute_xx_xxxxxx
AI
EHS_Period_kWh_xx_xxxxxx
AI
EHS_Period_Minute_xx_xxxxxx
AI
EHS_WOCurrentTemp_xx_xxxxxx
AI
EHS_HotWaterTemp_xx_xxxxxx
BI
EHS_ControlTempType_xx_xxxxxx
BI
EHS_Thermostat_xx_xxxxxx
BI
EHS_GoOut_xx_xxxxxx
BV
EHS_Power_xx_xxxxxx
BV
EHS_Cool_LimitTemp_Set_xx_xxxxxx
BV
EHS_Heat_LimitTemp_Set_xx_xxxxxx
BV
EHS_WOCoolLimitFlag_xx_xxxxxx
BV
EHS_WOHeatLimitFlag_xx_xxxxxx
BV
EHS_WTHeatLimitFlag_xx_xxxxxx
BV
EHS_HotWater_Power_xx_xxxxxx
BV
EHS_Sleep_xx_xxxxxx
MV
EHS_Operation_Mode_xx_xxxxxx
MV
EHS_Mode_Limit_xx_xxxxxx
MV
EHS_Remocon_Limit_xx_xxxxxx
MV
EHS_HotWater_Mode_xx_xxxxxx
AI
EHS_Error_Code_xx_xxxxxx
NC
EHS_Notify_xx_xxxxxx
Unit
Object Name
Inactive Active
Text-1 Text-2
°C
Use when displayed temperature type
°C
Use when displayed temperature type
°C
°C
Use when displayed temperature type
°C
Use when displayed temperature type
°C
°C
°C
°C
kWh
Minute
kWh
Minute
°C
°C
Room WaterOut
False
Off
Off
False
False
False
False
False
Off
Off
Auto
Cool
Cool
No Limit
Only
Disable
Enable RC
Force
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
Status value
Text-3
Text-4
is set to 'Room' .
is set to 'WaterOut' .
is set to 'Room' .
is set to 'Room' .
True
On
On
Use when displayed tempera-
True
ture type is set to 'Room' .
Use when displayed tempera-
True
ture type is set to 'Room' .
Use when displayed tempera-
True
ture type is set to 'WaterOut' .
Use when displayed tempera-
True
ture type is set to 'WaterOut' .
True
On
On
Heat
Heat Only
Conditional
RC
RC
Eco
Standard
Power
2013-04-25 오전 10:14:42