3.0 INSTALLATION

All inner exhaust and outer intake vent pipe joints may be sealed using either red RTV high temp
silicone sealant W573-0002 (not supplied) or black high temp mill pac W573-0007 (not supplied) with
the exception of the fireplace exhaust flue collar which must be sealed using mill pac.
If using pipe clamps to connect vent components, 3 screws must also be used to ensure the
Risk of fire, explosion or asphyxiation. Improper support of the entire venting system may allow vent
to sag and separate. Use vent runs support and connect vent sections per installation instructions.
Risk of fire, do not allow loose materials or insulation to touch the vent pipe. Remove insulation to
allow for the installation of the attic shield and to maintain clearances to combustibles.
3.1

wALL ANd CEILINg prOTECTION

Do not fill the space between the vent pipe and enclosure with any type of material. Do not pack insulation or
combustibles between ceiling firestops. Always maintain specified clearances around venting and firestop
systems. Install wall shields and firestops as specified. Failure to keep insulation or other materials away from
For optimum performance it is recommended that all horizontal runs have a minimum of 1/4" rise per foot using
flexible venting. For safe and proper operation of the fireplace, follow the venting instructions exactly.
3.2

hOrIzONTAL INSTALLATION

This application occurs when venting through an exterior wall. Having
determined the correct height for the air terminal location, cut and frame
a hole in the exterior wall 14 1/2" wide by 14 1/2" high to
accommodate the firestop assembly. Dry fit the firestop
assembly before proceeding to ensure the brackets on
the rear surface fit to the inside surface of the horizontal
framing.
NOTE: The firestop assembly must be installed with the
vent shield to the top.
The length of the vent shield may be cut shorter for combustible
walls that are less than 8 1/2" thick but the vent shield must extend
the full depth of the combustible wall.
A. Apply a bead of caulking (not supplied) around the edge of the inside
surface of the firestop assembly, fit the firestop assembly to the hole
and secure using the 4 screws (supplied in your manual baggie).
B. Once the vent pipe is installed in its final position, apply high temperature sealant W573-0007 (not
supplied) between the pipe and the firestop.
NOTE: Do not fill the cavity between the pipe and the framing with any type of material.
Tp - HORIZONTAL INSTALLATION
Tp - VERTICAL INSTALLATION
W415-0687 / 12.02.08
Follow the venting instructions exactly.
connection cannot slip off.
Do not clamp the flexible vent pipe.
vent pipe may cause fire.
The firestop assembly must be installed with the vent shield to the top.
WARNING
!
WARNING
!
WARNING
!
SHIELD
CAULKING
FIRESTOP
SPACER
fIGURE 3.2a
VENT
14 1/2"
14 1/2"
FINISHING
MATERIAL
DETERMINE
THE
CORRECT
HEIGHT