Toshiba RAS-M10GDCV-E Installation Manual
Toshiba RAS-M10GDCV-E Installation Manual

Toshiba RAS-M10GDCV-E Installation Manual

Toshiba air conditioner (multi-split type)
Hide thumbs Also See for RAS-M10GDCV-E:
Table of Contents

Advertisement

AIR CONDITIONER

CLIMATISEUR (TYPE MULTI-SPLIT)
KLIMAGERÄT (MULTI-SPLIT SYSTEM)
CONDIZIONATORE D'ARIA (TIPO MULTIAMBIENTI)
AIRE ACONDICIONADO (TIPO MULTI-SPLIT)
CONDICIONADOR DE AR (TIPO COM MÚLTIPLA DIVISÃO)
ΚΛΙΜΑΤΙΣΤΙΚΟ (TΥΠΟΣ MULTI-SPLIT)
Cooling Only Model
Modèle à froid seul
Geräte nur zur Kühlung
Modello solo per raffreddamento
Modelo de refrigeración únicamente
Modelo Apenas para Refrigeração
Μοντέλο Ψύξης αποκλειστικά
Heat Pump Model
Modèle à thermopompe
Geräte mit Heizung
Modello con pompa di riscaldamento
Modelo con bomba de calor
Modelo da Bomba de Calor
Μοντέλο µε Αντλία Θερµότητας

INSTALLATION MANUAL

MANUEL D'INSTALLATION
INSTALLATIONS-HANDBUCH
MANUALE DI INSTALLAZIONE
MANUAL DE INSTALACIÓN
MANUAL DE INSTALAÇÃO
ΕΓΧΕΙΡΙ∆ΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
(MULTI-SPLIT TYPE)
Concealed Duct Type
Type à conduits dissimulés
Luftkanal verborgen montiert
Tipo a condotto nascosto
Modelo con conductos ocultos
Tipo com Conduto Embutido
Τύπος συγκεκαλυµµένου
αγωγού
Indoor Unit
Unité intérieure
Raumeinheit
Unità interna
Unidad interior
Unidade interna
Εσωτερική µονάδα
RAS-M10GDCV-E
RAS-M13GDCV-E
RAS-M16GDCV-E
RAS-M10GDV-E
RAS-M13GDV-E
RAS-M16GDV-E
Outdoor Unit
Unité extérieure
Außeneinheit
Unità esterna
Unidad exterior
Unidade externa
Εξωτερική µονάδα
RAS-M14GACV-E
RAS-M18GACV-E
RAS-3M23GACV-E
RAS-4M27GACV-E
RAS-M14GAV-E
RAS-M18GAV-E
RAS-3M26GAV-E
RAS-4M27GAV-E

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAS-M10GDCV-E

  • Page 1: Installation Manual

    Außeneinheit Unità interna Unità esterna Unidad interior Unidad exterior Unidade interna Unidade externa Εσωτερική µονάδα Εξωτερική µονάδα Cooling Only Model RAS-M10GDCV-E RAS-M14GACV-E Modèle à froid seul RAS-M13GDCV-E RAS-M18GACV-E Geräte nur zur Kühlung RAS-M16GDCV-E RAS-3M23GACV-E Modello solo per raffreddamento RAS-4M27GACV-E Modelo de refrigeración únicamente Modelo Apenas para Refrigeração...
  • Page 2: Table Of Contents

    CONTENTS/SOMMAIRE/INHALT/INDICE/CONTENIDO ENGLISH 1 SAFETY PRECAUTIONS............1 Please read this Installation Manual carefully before installing the 2 ACCESSORY PARTS AND PARTS TO BE PROCURED Air Conditioner. LOCALLY .................. 3 3 SELECTION OF INSTALLATION PLACE......... 4 • This Manual describes the installation method of the indoor unit. 4 INSTALLATION OF INDOOR UNIT ..........
  • Page 3 ÍNDICE/ΠΕΡΙΕΧΟΜΕΝΑ PORTUGUÊS 1 PRECAUÇÕES DE SEGURANÇA..........1 Por favor, leia este Manual de Instalação atentamente, antes da 2 PARTES ACESSÓRIAS / PARTES A SEREM OBTIDAS instalação do Condicionador de Ar. LOCALMENTE ................3 3 SELEÇÃO DO LOCAL DE INSTALAÇÃO......... 4 •...
  • Page 5: Safety Precautions

    1 SAFETY PRECAUTIONS Power supply cord of outdoor unit shall be 2.5 mm (H07RN-F or 60245IEC66) polychloroprene sheathed flexible cord. • Read this “SAFETY PRECAUTIONS” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. •...
  • Page 6 • When installing the air conditioner in a small room, provide appropriate measures to ensure that the concentration of refrigerant in the room does not exceed the critical level should leakage occur. It is not dangerous refrigerant; it has not toxicity or combustibility. However, a concentration above 0.3 kg/m³ as criterion still causes suffocation.
  • Page 7: Accessory Parts And Parts To Be Procured Locally

    • Connecting pipe (Gas side) (12.7 mm (diam.), Nominal (diam.) 1/2" thick 0.8 mm) RAS-M16GDCV-E, RAS-M16GDV-E (9.52 mm (diam.), Nominal (diam.) 3/8" thick 0.8 mm) RAS-M10GDCV-E, RAS-M10GDV-E, RAS-M13GDCV-E, RAS-M13GDV-E • Power supply cord 2.5 mm (H07RN-F or 60245IEC66) • Connecting cable 1.0 mm...
  • Page 8: Selection Of Installation Place

    3 SELECTION OF INSTALLATION PLACE WARNING • Install the air conditioner where there is sufficient strength to withstand the weight of the unit. If the strength is not sufficient, the unit may fall down resulting in injury. • Install the air conditioner at a position keeping the height by 2.5 m or more from the floor. If you insert your hands or others directly into the unit during running of the air conditioner, it is dangerous because you may contact with revolving fan or active electricity.
  • Page 9: Installation Of Indoor Unit

    4 INSTALLATION OF INDOOR UNIT WARNING Install the air conditioner certainly at a place to sufficiently withstand the weight. If the strength is insufficient, the unit may fall down resulting in human injury. Perform a specified installation work to guard against an earthquake. An incomplete installation can cause accidents by the units falling and dropping.
  • Page 10 External view REQUIREMENT The hanging bolt pitch on longitudinal direction is not divided at center with the ceiling opening size. Therefore, check the relational position in the following figure. 650 (Inside flange) 730 (Hanging bolt pitch) 640 (Inside flange) 19.7 Hanging down of indoor unit Refer to installation figures of hanging material and hanging bolt.
  • Page 11 Concealed duct type C channel Supply chamber Supply grille Supply grille Supplying Air filter 200 mm (diam.) round duct Supplying Indoor unit Returning Return air panel Ledge ceiling concealed duct type Supply grille Supplying Supply grille Indoor unit Supply Supplying chamber Air filter 200 mm (diam.)
  • Page 12: Air Ducting Work

    5 AIR DUCTING WORK Static pressure characteristics of each model Fig. 2 RAS-M13GDCV-E, RAS-M13GDV-E Fig. 1 RAS-M10GDCV-E, RAS-M10GDV-E High tap Upper limit of external static Upper limit of pressure Air volume external static limit pressure Air volume limit (Minimum) (Minimum) 380 m³/hr.
  • Page 13 Installation reference The air supply ducting work is classified into two ways, one is branched by the square ducts, and the other is branched by the round ducts. (Be sure to divide the air supply duct into three or more branches.) Square duct In case of using the square duct, apply the thermal insulator of thickness by 25 mm or more to the duct board.
  • Page 14 Square duct Round duct Thermal insulator with Thermal insulator with sticking Thermal insulator at indoor Thermal insulator at indoor sticking material material unit side unit side (50 mm-width, 6 mm (t)) (50 mm-width, 6 mm-thickness) (Stuck already at shipment (Stuck already at shipment Aluminum tape from the factory) from the factory)
  • Page 15 Points at installation work General cautions Considering installation places of indoor unit and supply chamber, and structure of the building, determine the duct path. In order to utilize the static pressure characteristics of the air supply in the indoor unit, design the duct branching by setting size up to the air supply chamber or by setting length to the first branch as long as possible (Min.
  • Page 16: Drain Piping Work

    6 DRAIN PIPING WORK Piping material • For laying pipes under ground, use hard vinyl chloride pipe. (Inner diam. 20 or 25 mm) Piping and cautions • Set drain side of pipe at downward slope. (1/100 or more) • Be sure to apply thermal insulation (foaming polyethylene, 10 mm-thickness or 1.5 m to 2 m Indoor more) for pipes passing through the room.
  • Page 17: Refrigerant Piping

    7 REFRIGERANT PIPING Refrigerant Piping If the outdoor units are to be mounted on a wall, make sure that the platform supporting is sufficiently strong. The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration should be given to ensuring that the outdoor unit will not fall.
  • Page 18 Tightening connection Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure. CAUTION • Do not apply excess torque. Otherwise, the nut may crack depending on the conditions. (Unit: N·m) Flare at indoor Outer diameter of copper pipe...
  • Page 19: Evacuating

    8 EVACUATING EVACUATION Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of vacuum pump. Use a vacuum pump Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops.
  • Page 20: Electrical Work

    9 ELECTRICAL WORK For the air conditioner that has no power cord. NOTE For selection and connection method of the power supply cords, refer to the details in the Installation Manual of the outdoor unit. CAUTION • If incorrect/incomplete wiring is carried out, it will cause an electrical fire or smoke. •...
  • Page 21: Check And Test Operation

    Check and Test Operation Be sure to test the piping connections for gas leaking. • Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a leak detector or soap water. Flare nut connections (Indoor unit) •...
  • Page 22: Installation/Servicing Tools

    10 INSTALLATION/SERVICING TOOLS Tools Tools Applicable to R22 model Gauge manifold Charge hose Electronic balance for refrigerant charging Torque wrench (nominal diam. 1/2, 5/8) Flare tool (clutch type) Gauge for projection adjustment — — Vacuum pump adapter Gas leakage detector : Newly prepared (They are special requirements for R410A, separated from those for R22.) ! : Existing tools are available.
  • Page 23 EG25540501-c...

Table of Contents