  • Page 1 0157385en 0908 Generator GV 2500A OPERATOR’S MANUAL...
  • Page 2: Carbon Monoxide

    DANGER CARBON MONOXIDE Using a generator indoors CAN KILL YOU IN MINUTES. Generator exhaust contains carbon monoxide (CO). This is a poison you cannot see or smell. If you can smell the generator exhaust, you are breathing CO. But even if you cannot smell the exhaust, you could be breathing CO.
  • Page 3: Table Of Contents

    GV 2500A Table of Contents Foreword Safety Information Operating Safety .................. 7 Operator Safety while using Internal Combustion Engines ....8 Service Safety ..................9 Label Locations .................. 10 Safety and Operating Labels .............. 11 Operation Determining Power Requirements ............. 13 Installation ..................
  • Page 4 Table of Contents GV 2500A Technical Data Generator ....................32 Engine ....................33 Sound Specifications ................33 wc_bo0157385en_004TOC.fm...
  • Page 5: Foreword

    Foreword Foreword This manual provides information and procedures to safely operate and maintain this Wacker Neuson model. For your own safety and protection from injury, carefully read, understand and observe the safety instructions described in this manual. Keep this manual or a copy of it with the machine. If you lose this manual or need an additional copy, please contact Wacker Neuson Corporation.
  • Page 6: Safety Information

    Safety Information GV 2500A Safety Information This manual contains DANGER, WARNING, CAUTION, NOTICE and NOTE callouts which must be followed to reduce the possibility of personal injury, damage to the equipment, or improper service. This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
  • Page 7: Operating Safety

    GV 2500A Safety Information Operating Safety BACKFEED FROM THE GENERATOR INTO THE PUBLIC POWER DISTRIBUTION SYSTEM CAN CAUSE SERIOUS INJURY OR DEATH TO UTILITY WORKERS! DANGER Improper connection of generator to a building’s electrical system can allow electrical current from the generator to backfeed into utility lines.
  • Page 8: Operator Safety While Using Internal Combustion Engines

    Safety Information GV 2500A 2.1.10 ALWAYS be sure the machine is on a firm, level surface and will not tip, roll, slide, or fall while operating. 2.1.11 ALWAYS transport the generator in an upright position. 2.1.12 ALWAYS keep the machine at least one meter (three feet) away from structures, buildings, and other equipment during use.
  • Page 9: Service Safety

    GV 2500A Safety Information Service Safety Poorly maintained equipment can become a safety hazard! In order for the equipment to operate safely and properly over a long period of time, periodic maintenance and occasional repairs are necessary. If WARNING the generator is experiencing problems or is being serviced, attach a “DO NOT START”...
  • Page 10: Label Locations

    Safety Information GV 2500A Label Locations HOT ! PETROL BENZIN CALDO ! D A N G E R G E F A H R P E L I G R O D A N G E R wc_gr001289 wc_si000106gb.fm...
  • Page 11: Safety And Operating Labels

    GV 2500A Safety Information Safety and Operating Labels Wacker Neuson machines use international pictorial labels where needed. These labels are described below: Label Meaning WARNING! Hot surface! HOT ! CALDO ! Close the choke. Gasoline PETROL BENZIN Potential Earth. WARNING! Electric shock will cause serious injury or death.
  • Page 12 Safety Information GV 2500A Label Meaning DANGER! Asphyxiation hazard. Read the Operator’s D A N G E R Manual for instructions. G E F A H R P E L I G R O D A N G E R...
  • Page 13: Operation

    Check with your nearest Wacker Neuson dealer, or contact the manufacturer or dealer of the tool or appliance, if you have questions regarding power requirements.
  • Page 14 Operation GV 2500A Approximate Starting Power Requirements • Incandescent lights and appliances such as irons and hot plates, which use a resistive-type heating element, require the same wattage to start and run as is stated on their nameplates. • Fluorescent and mercury lamps require 1.2–2 times their stated watt- age to start.
  • Page 15: Installation

    GV 2500A Operation Installation Place the generator in an area where it will not be exposed to rain, snow, or direct sunlight. Make sure it is positioned on firm, level ground, so it will not slide or shift. Position the engine exhaust away from areas where people may be present.
  • Page 16: Generator Derating

    Operation GV 2500A Generator Derating All generators are subject to derating for altitude and temperature. Internal combustion engines, unless modified, run less efficiently at higher altitudes due to the reduction of air pressure. This translates into a lack of power and thus reduction in generator output.
  • Page 17: Grounding The Generator

    GV 2500A Operation Grounding the Generator The neutral of this machine is not connected to ground. Under standard operating conditions, do not connect the frame PE stud to earth ground. Refer to local codes if machine is used to power a CAUTION building or similar distribution system.
  • Page 18: Use Of Extension Cords

    Operation GV 2500A Use of Extension Cords When a long extension cord is used to connect an appliance or tool to the generator, a voltage loss occurs—the longer the cord, the greater the voltage loss. This results in less voltage being supplied to the appliance or tool and increases the amount of current draw or reduces performance.
  • Page 19 GV 2500A Operation Minimum Extension Cord SizeTable Minimum Extension Cord Size 230V/1~/50Hz 400V/3~/50Hz Length m Length m Rating Cross sectional area of wire in mm Minimum Extension Cord Size Graph 1000 2000 3000 4000 5000 6000 A x m wc_tx000269gb.fm...
  • Page 20: Control Panel

    Operation GV 2500A Control Panel See Graphic: wc_gr001251 The circuit breaker protects the generator from severe overloads or short circuits. If the circuit breaker opens, turn the engine off immediately and determine the cause before restarting. Check the appliances and tools attached to the generator for defects and make sure their power requirements do not exceed the power rating of the generator or the current limit of the receptacles.
  • Page 21: Before Starting

    GV 2500A Operation Before Starting 3.8.1 Read and understand safety and operating instructions at beginning of this manual. 3.8.2 Read and understand the meanings of all warning and operating labels. 3.8.3 Check: • oil level in engine. • fuel level.
  • Page 22: To Start

    Operation GV 2500A To Start See Graphic: wc_gr001279 3.9.1 Disconnect all loads from the generator. 3.9.2 Open fuel valve (a). Note: If engine is cold, move choke lever to closed position (b1). If engine is hot, set choke to open position (b2).
  • Page 23: Maintenance

    GV 2500A Maintenance Maintenance Engine Maintenance The chart below lists basic machine and engine maintenance. Refer to your engine Operator’s Manual for additional information on engine maintenance. Periodic Maintenance Schedule Daily After Every Every Every before first starting 20 hrs.
  • Page 24: Engine Oil

    Maintenance GV 2500A Engine Oil See Graphic: wc_gr000022 4.3.1 Drain the oil while the engine is still warm. 4.3.2 Remove the oil filler plug (a) and the drain plug (b) to drain the oil. Note: In the interests of environmental protection, place a plastic sheet and a container under the machine to collect any liquid that drains off.
  • Page 25: Air Cleaner

    GV 2500A Maintenance Air Cleaner See Graphic: wc_gr0001287 The engine is equipped with a single element air cleaner. Service air cleaner frequently to prevent carburetor malfunction. NOTICE: NEVER run the engine without the air cleaner. Severe engine damage will occur.
  • Page 26: Spark Plug

    Maintenance GV 2500A Spark Plug See Graphic: wc_gr000028 Clean or replace the spark plug as needed to ensure proper operation. Refer to your engine operator’s manual. The muffler becomes very hot during operation and remains hot for a while after stopping the engine. Do not touch the muffler while it is hot.
  • Page 27: Engine Speed

    GV 2500A Maintenance Engine Speed See Graphic: wc_gr001288 Generators require a fixed engine speed to maintain the correct voltage. Engine speed is controlled by a governor which automatically adjusts to varying loads on the engine to maintain a constant speed of 3000 rpm.
  • Page 28: Carburetor Adjustment

    Maintenance GV 2500A Carburetor Adjustment See Graphic: wc_gr0001061 The pilot screw (a) is fitted with a limiter cap to prevent excessive enrichment of the air-fuel mixture in order to comply with emission regulations. The mixture is set at the factory and no adjustment should be necessary.
  • Page 29: Storage

    GV 2500A Maintenance Storage Before storing the generator for a long period of time: 4.8.1 Close the fuel valve and remove and empty the sediment cup or fuel strainer. 4.8.2 Disconnect the fuel line from the carburetor. Place the open end of the fuel line into a suitable container and open the fuel valve to drain the fuel from the tank.
  • Page 30: 4.10 Troubleshooting

    Maintenance GV 2500A 4.10 Troubleshooting Problem / Symptom Reason / Remedy If engine doesn't start, check • Engine switch is on "Start". that: • Fuel valve is open. • Fuel tank has fuel. • Choke lever is in correct position. Choke should be closed when starting a cold engine.
  • Page 31: 4.11 Wiring Diagram

    GV 2500A Maintenance 4.11 Wiring Diagram See graphic: wc_gr001290 wc_gr001290 Ref. Description Ref. Description Main Windings Diode Auxiliary Winding Surge Absorber Capacitor Circuit Breaker Rotor Windings Receptacle 230V, 16 Amp Wire Colors Black Violet Orange Green White Purple Blue Yellow...
  • Page 32: Technical Data

    Technical Data GV 2500A Technical Data Generator Item No. 0009345 0009350 0009355 0009360 GV 2500A Generator Maximum Output 2120 Continuous Output 2070 Type Single voltage, single phase, Brushless, capacitor regulator system AC Voltages Available Volts phase 1ø Frequency Power Factor...
  • Page 33 GV 2500A Technical Data Engine Engine Power Rating Net power rating per SAE J1349. Actual power output may vary due to conditions of specific use. Model GV 2500A Engine Engine Make Honda Engine Model GX160K1-VPM4 Max. rated power @ kW (Hp) 3.6 (4.8) @ 3600 rpm...
  • Page 35: Ec Declaration Of Conformity

    EC DECLARATION OF CONFORMITY CE-KONFORMITÄTSERKLÄRUNG DECLARACIÓN DE CONFORMIDAD DE LA CE DÉCLARATION DE CONFORMITÉ C.E. WACKER NEUSON CORPORATION, N92 W15000 ANTHONY AVENUE, MENOMONEE FALLS, WISCONSIN USA WACKER CONSTRUCTION EQUIPMENT AG AUTHORIZED REPRESENTATIVE IN THE EUROPEAN UNION BEVOLLMÄCHTIGTER VERTRETER FÜR DIE EUROPÄISCHE GEMEINSCHAFT Preußenstraße 41...
  • Page 36 Fax: +49 - (0)89-3 54 02-3 90 Wacker Neuson Corporation · P.O. Box 9007 · Menomonee Falls, WI 53052-9007 · Tel. : (262) 255-0500 · Fax: (262) 255-0550 · Tel. : (800) 770-0957 Wacker Asia Pacific Operations · Skyline Tower, Suite 2303, 23/F · 39 Wang Kwong Road, Kowloon Bay, Hong Kong · Tel. +852 2406 60 32 · Fax: +852 2406 60 21...