High- -Voltage Connections; Special Procedures For 208V Operation; Control Voltage Connections - Bryant Legacy 704D--A Installation Instructions Manual

13 seer single--packaged air conditioner system with puron (r--410a) refrigerant single and three phase 2--5 nominal tons (sizes 24--60)
Table of Contents

Advertisement

CAUTION
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit being installed.
1. Make all electrical connections in accordance with
NFPA 70 (NEC) (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field- -supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high- -voltage power to unit is within
operating voltage range indicated on unit rating plate. On
3- -phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of
improper voltage and/or phase imbalance.
4. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit,
etc.
HIGH- - VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a
field- -supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field- -supplied disconnect may be mounted on the unit over
the high- -voltage inlet hole when the standard power and
low- -voltage entry points are used. See Fig. 2 and 3 for acceptable
location.
See unit wiring label (Fig. 12, 13 and 14) and Fig. 10 for reference
when making high voltage connections. Proceed as follows to
complete the high- -voltage connections to the unit.
Single phase units:
1. Run the high- -voltage (L1, L2) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
3-PHASE SHOWN
1-PHASE USES
TWO POWER
EQUIP GR
LEADS
CONTROL BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
SPLICE BOX
Fig. 10 - - High- - and Control- -Voltage Connections
5. Connect field wire L2 to yellow wire on connection 23 of
the compressor contactor.
Three- -phase units:
1. Run the high- -voltage (L1, L2, L3) and ground lead into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5. Connect field wire L3 to yellow wire on connection 13 of
the compressor contactor.
6. Connect field wire L2 to blue wire from compressor.
SPECIAL PROCEDURES FOR 208- - V OPERATION
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main
power to system and install lockout tag. With disconnect
switch open, move black wire from transformer (3/16
in.)(4.8 mm) terminal marked 230 to terminal marked 208.
This retaps transformer to primary voltage of 208 vac.

CONTROL VOLTAGE CONNECTIONS

NOTE: Do not use any type of power- -stealing thermostat. Unit
control problems may result.
Use no. 18 American Wire Gage (AWG) color- -coded, insulated
(35°C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft (30.5 m) from the unit (as measured along the
control voltage wires), use no. 16 AWG color- -coded, insulated
(35° C minimum) wires.
9
POWER
SUPPLY
FIELD-SUPPLIED
FUSED DISCONNECT
WHT(W1)
W1
VIO (W2)
W2
YEL(Y)
Y
GRN(G)
G
THERMOSTAT
RED(R)
R
(TYPICAL )
BRN(C)
C
BLU (DH)
DH
GRA (Y2)
3-Phase
Only
A09066

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents