Rig And Place Unit; Inspection - Bryant Legacy 704D--A Installation Instructions Manual

13 seer single--packaged air conditioner system with puron (r--410a) refrigerant single and three phase 2--5 nominal tons (sizes 24--60)
Table of Contents

Advertisement

CAUTION - NOTICE TO RIGGERS
PRUDENCE - AVIS AUX MANIPULATEUR
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
SEE DETAIL A
VOIR DÉTAIL A
SMALL CABINET
24
Unit*
lb
kg
Rigging
279
127
Weight
* For 460 volt units, add 14 lb (6.35 kg) to the rigging weight.
NOTE: See dimensional drawing for corner weights.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier. If a plenum return is used on a
vertical unit, the return should be ducted through the roof deck to
comply with applicable fire codes. See unit rating plate for any
required clearances around ductwork. Cabinet return- -air static
shall not exceed - -.25 IN. W.C.
Step 5 — Rig and Place Unit
Rigging and handling of this equipment can be hazardous for
many reasons due to the installation location (roofs, elevated
structures, etc.).
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment,
and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but
not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the
lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting
kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work
gloves.

INSPECTION

Prior to initial use, and at monthly intervals, all rigging shackles,
clevis pins, and straps should be visually inspected for any damage,
evidence of wear, structural deformation, or cracks. Particular
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
MINIMUM HEIGHT: 36" (914.4 mm)
HAUTEUR MINIMUM
UNIT HEIGHT
HAUTEUR D'UNITÉ
30
36
lb
kg
lb
kg
284
129
290
132
Fig. 5 - - 704D- -- -A Unit Suggested Rigging
DUCTS
SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
UNIT ON ROOF CURB
DETAIL A
VOIR DÉTAIL A
LARGE CABINET
42
Unit*
lb
kg
Rigging
378
171
Weight
attention should be paid to excessive wear at hoist hooking points
and load support areas. Materials showing any kind of wear in
these areas must not be used and should be discarded.
A
B
A-B
1/4
Fig. 6 - - Unit Leveling Tolerances
WARNING
!
UNIT FALLING HAZARD
Failure to follow this warning could result in personal
injury or death.
Never stand beneath rigged units or lift over people.
1. Leave top shipping skid on the unit for use as a spreader bar
to prevent the rigging straps from damaging the unit. If the
skid is not available, use a spreader bar of sufficient length
to protect the unit from damage.
6
BANDE SCELLANT DOIT ÊTRE
EN PLACE AVANT DE PLACER
L'UNITÉ SUR LA BASE DE TOIT
50CY502286 2.0
48
60
lb
kg
lb
384
174
406
C
MAXIMUM ALLOWABLE
DIFFERENCE in. (mm)
B-C
A-C
(6.35)
(6.35)
(6.35)
1/4
1/4
A09051
kg
184
A07925

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents