Make Duct Connections —
ductwork to and from unit in accordance with all applicable
codes. Duct construction must allow unit to operate within duct
external static pressure limits as shown on job submittals and in
Tables 5 and 6. Duct opening should be the same size as the
unit. For 40UH units ducted to multiple openings, allow ade-
quate straight duct, as shown below, immediately after the unit.
40UH
075
Minimum Straight Duct
Required (Length in ft)
Units designed to operate with ductwork may be damaged
if operated without intended ductwork attached.
Ensure that units ducted to multiple openings have sufficient
straight duct immediately after the unit.
FACTORY SETTINGS — CHILLED WATER COIL APPLICATIONS
Unit
40UV050
40UV,UH075
40UV,UH100
40UV,UH125
40UV,UH150
FACTORY SETTINGS — ELECTRIC HEAT/DX COIL APPLICATIONS
Unit
40UV050
40UV,UH075
40UV,UH100
40UV,UH125
40UV,UH150
LEGEND
CX
— Chilled Water Applications
DX
— Direct Expansion
HW
— Hot Water
*Standard on sizes 050-150.
If applicable, install all
100
125
150
200
45
52
58
63
75
Table 5 — Unit Ventilator Airflow — PSC Motor*
Speed
1-row
2-row
Max
522
High
503
Low
458
Max
806
High
682
Low
569
Max
1064
1033
High
662
Low
530
Max
1295
1285
High
899
Low
568
Max
1542
1480
High
1071
1068
Low
812
Speed
1-row
2-row
Max
522
High
503
Low
458
Max
806
High
682
Low
569
Max
1064
1033
High
794
Low
662
Max
1295
1285
High
1055
1040
Low
738
Max
1542
1480
High
1285
1257
Low
934
Units provided with outside air must utilize the low-
temperature safety switch to prevent coil freeze-up.
Insulate all ductwork as required. Use flexible connections
to minimize duct-to-unit alignment problems and noise trans-
mission where specified.
Install ductwork, grilles, and plenums so that they do not re-
strict access to filter.
Cut openings for supply and return air grilles, thermostats,
and switch plates where specified on job drawings. Be careful
not to cut wires, piping, or structural supports. Use a steel ther-
mostat shield ring to protect drywall from thermostat wiring
where applicable.
Prevent dust and debris from settling in unit. If wall finish or
color is to be applied by spraying, cover all openings to
prevent spray from entering unit.
Approximate Air Delivery (Cfm)
3-row
4-row
510
497
485
490
476
464
449
440
425
778
750
747
664
645
629
554
539
527
1001
1013
659
655
642
519
507
503
1215
1218
930
876
865
616
597
570
1500
1484
1065
1034
801
790
881
Approximate Air Delivery (Cfm)
3-row
4-row
510
497
485
490
476
464
449
440
425
778
750
747
664
645
629
554
539
527
1001
1013
788
782
773
659
655
642
1215
1218
1024
995
767
732
719
1500
1484
1229
1248
928
922
901
NOTE: Use the table below to determine the heating and cooling coil
combinations available with PSC Motor operation.
COOLING COIL
5 Rows CW
4 Rows CW
3 Rows CW or DX†
†DX cooling applications are only available in 3-row cooling
configuration.
23
5-row
6-row
490
489
473
476
452
455
766
732
621
596
533
514
973
980
763
740
498
501
1239
1250
852
846
568
558
1468
1482
1033
1031
848
842
5-row
6-row
490
489
452
455
410
414
766
732
621
596
533
514
973
980
857
834
628
620
1239
1250
1099
1091
987
986
1468
1482
1246
1239
1033
1031
HEATING COIL
HW
Steam
Electric
1 or 2 rows
N/A
3 elements
3 rows
1 or 2 rows
4 elements
4 rows
1 or 2 rows
5 or 6 elements
7-row
457
444
430
697
570
495
967
717
504
1175
846
573
1374
1013
799
7-row
457
430
406
697
570
495
967
810
611
1175
1052
964
1374
1199
1013