Hyundai HSH-P182NDC Service Manual page 30

Split type
Table of Contents

Advertisement

7
.
C
H
E
C
K
I
N
G
C
7
.
C
H
E
C
K
I
N
G
C
Notes:
1) Please don't hold motor by lead wires.
2) Please don't plug IN/OUT the motor connector while power ON.
3) Please don't drop .Hurl or dump motor against hard material.Malfunction may not be
observed at early stage after such shock.But it may be found later,This type of mishandling
void our warranty.
4) The wiring color of the motor may not be identical with the picture shows, please take the
actual material as standard.
3. COMPRESSOR
1.Coil Resistance: 1.54Ω(main)/2.48Ω(aux)
Test in resistance.
TOOL: Multimeter.
Test the resistance of the winding. The compressor is fault if the resistance of winding
0(short circuit)or∞(open circuit)
Familiar trouble: 1)Compressor motor lock. 2)Discharge pressure value approaches static
pressure value .3)Compressor motor winding abnormality.
Notes:1)Don't put a compressor on its side or turn over.
2) Please assembly the compressor in your air conditioner rapidly after removing the
plugs.Don't place the comp. In air for along time.
3) Avoiding compressor running in reverse caused by connecting electrical wire
incorrectly.
4. STEPPER MOTOR
4.1 LUVER MOTOR
Resistance per phase:200Ω±7%
(
5 red
O
M
P
O
N
E
N
T
S
O
M
P
O
N
E
N
T
S
M
)
(
) 1 blue
3 yellow
(
)
28