Unit physical data

Size
Cooling capacity (BTU/hr)
Heating capacity (BTU/hr)
Compressor (1 each)
Factory refrigerant charge R-410A (oz)
Fan data
Speeds
Blower wheel size (D x W) (in.)
standard/high static
Air flow (CFM @ 0.0" of static pressure)
Water/condensate side data
Flow rate (GPM)
Water connection size (female NPT, in.)
Water side pressure drop (psi)
Condensate connection size (in.)
Air coil data
Total face area (ft.)
Tube size (in.)
Fin spacing (FPI)
Number of rows
Cabinet data
Depth (in.)
Height (in.)
Width (in.)
Filter standards - washable filter (in.)
Cabinet weight (lb.)
Chassis weight (lb.)
Notes:
Capacities based on a water loop application at
AHRI/ASHRAE/ISO 13256-1 specifications.
Cooling capacity based upon 80.6 °F DB, 66.2 °F WB entering air
temperature.
6
09
12
15
9200
12000
16500
12500
16000
21500
Rotary
Rotary
Rotary
27.5
31.7
45.8
2
2
7.1 x 6.7
7.1 x 6.7
7.1 x 6.7
360
420
540
2.6
3.6
4.9
1/2
1/2
3/4
4.5
6.2
5.8
3/4
3/4
3/4
1.48
1.48
1.81
3/8
3/8
3/8
14
14
14
2
3
18
18
18
88
88
88
18
18
18
14-1/4 x
14-1/4 x
14-1/4 x
18-1/2
18-1/2
22-1/2
120
120
120
99
105
119
18
24
18500
22500
23500
29500
Rotary
Rotary
47.0
52.9
2
2
2
7.1 x 6.7
9.2 x 10.0
630
820
5.3
6.6
3/4
3/4
6.5
5.0
3/4
3/4
1.81
1.72
3/8
3/8
14
12
4
4
3
18
24
88
88
18
24
14-1/4 x
19 x
22-1/2
28-3/4
120
170
122
187
Heating capacity based upon 68 °F DB, 59 °F WB entering air
temperature.
All ratings based upon air flow at high speed and operation at
lower voltage (208V) of dual voltage ratings.
30
36
30000
34000
37000
41000
Rotary
Scroll
64.6
60.0
2
2
9.2 x 10.0
9.2 x 10.0
1080
1220
8.7
9.4
3/4
3/4
7.3
7.8
3/4
3/4
1.72
1.72
3/8
3/8
12
12
4
4
24
24
88
88
24
24
19 x
19 x
28-3/4
28-3/4
170
170
198
225