Troubleshooting
PCB System Error Codes
(Green LEDs)
Warning = FLASHING
Lock-out = STEADY
LD1
LD2
LD3
OFF
OFF
OFF
X
OFF
OFF
X
OFF
OFF
X
OFF
OFF
X
OFF
OFF
X
X
OFF
X
OFF
OFF
X
OFF
OFF
X
X
OFF
X
X
OFF
58
System
Error
Code
Fault Description
(COM
T Stat)
LD4
High pressure lockout
X
Er 1
> 600 PSI
Low pressure lockout
OFF
Er 2
< 40 PSI
Freeze protection,
X
Er 4
water side
Freeze protection,
OFF
Er 5
air side, < 35°F
Er 9,
X
Condensate overflow
Er 10
Over/under low voltage
X
Er 11
protection
16VAC > voltage > 30VAC
OFF
Er 13
LWT sensor failure
X
Er 14
DAT sensor failure
OFF
Er 15
FP1 sensor failure
X
Er 16
FP2 sensor failure
Potential Causes
Low air flow (heating), low water flow (cooling)
Blower fan inoperable (heat mode)
Dirty air filter (heat mode)
Airflow by-passing air coil through due to poor sealing of
cabinet openings (heat mode)
Return air too hot (heat mode)
Air in risers (cool mode)
Dirty water strainer (cool mode)
Faulty zone valve (cool mode)
Mis-wired zone valve (cool mode)
Ball valves closed (cool mode)
Main water pump inoperable (cool mode)
Supply water too hot (cool mode)
Low refrigerant charge
Blower fan inoperable (cool mode)
Airflow by-passing air coil through due to poor sealing of
cabinet openings (cool mode)
Ball valves closed (heat mode)
Main water pump inoperable (heat mode)
Water temperature < 35°F or < 15°F (heating)
DIP switch 2 incorrectly set
Air in risers (heat mode)
Ball valves closed (heat mode)
Faulty zone valve (heat mode)
Main water pump inoperable (heat mode)
Dirty water strainer (heat mode)
Refrigerant charge quantity below factory recommendation
Blower failure (cooling)
Dirty air filter (cool mode)
Airflow by-passing air coil through due to poor sealing of
cabinet openings (cool mode)
Return air too cool (cool mode)
Refrigerant charge quantity above factory recommendation
Clogged drain line
Condensate switch has residual water contacting from unit
installation/removal
Loss of power, brown-out
Main power voltage not within acceptable range
Sensor wiring not properly connected
Sensor resistance above or below specification
Sensor wiring not properly connected
Sensor resistance above or below specification
Sensor wiring not properly connected
Sensor resistance above or below specification
Sensor wiring not properly connected
Sensor resistance above or below specification