Troubleshooting

Error Code
Fault Description
(commtstat)
High pressure lockout
> 600 psig
Low pressure lockout
< 40 psig
Freeze protection
H
O side
2
Freeze protection
air side < 35 °F
Condensate overflow
ER 9, ER 10
Over/under low
voltage protection,
18 VAC > voltage < 30VAC
LWT sensor failure
(low water temperature)
DAT sensor failure
(discharge air temperature)
FP1 sensor failure
(freeze protection)
FP2 sensor failure
(freeze protection)
Table G: Technical Diagnosis
System Warning (Flash)
LD1
LD2
LD3
ER 1
Off
Off
Off
ER 2
Off
Off
Flash
ER 4
Off
Off
Flash
ER 5
Off
Flash
Off
Off
Flash
Off
ER 11
Off
Flash
Flash
ER 13
Flash
Off
Off
ER 14
Flash
Off
Off
ER 15
Flash
Off
Flash
ER 16
Flash
Off
Flash
System Lockout (Steady On)
LD4
LD1
LD2
LD3
Flash
Off
Off
Off
Off
Off
Off
On
Flash
Off
Off
On
Off
Off
On
Off
Flash
Off
On
Off
Flash
Off
On
On
Off
N/a
N/a
N/a
Flash
N/a
N/a
N/a
Off
On
Off
On
Flash
On
Off
On
Possible Fault Cause
LD4
Low air flow (heating)
On
Low water flow (cooling)
Off
Low refrigerant charge
Water temperature
On
< 35 °F or < 15 °F (heating)
Off
Blower failure (cooling)
On
Clogged drain line
On
Loss of power, brown out
Sensor resistance above
N/a
or below specification
Sensor resistance above
N/a
or below specification
Sensor resistance above
Off
or below specification
Sensor resistance above
On
or below specification
Troubleshooting