Commissioning, inspection, maintenance
Further details regarding the individual steps
Returning the DHW cylinder into use
8
(cont.)
1. Reconnect the DHW cylinder to the
pipework.
2. Insert new gaskets H underneath
flange lid E or cylinder cap F.
3. Refit flange lid E or cylinder cap
F with stainless steel circular
blank G and tighten with the
required torque.
&
Cylinder cap: 160 Nm
&
Flange lid: 40 Nm
4. Fill the DHW cylinder from the DHW
side.
5. If the DHW cylinder is pressurised,
re-tighten the screws on flange lid
E with a torque of 40 Nm.
6. Fit thermometer sensor D, thermal
insulation mats C and hood B or
top panel A.