Gas-fired warm air furnace (type fsp category iv direct or non direct vent air furnace)
Table of Contents

Advertisement

2. Remove and save the two screws securing the junction box
to the side panel.
3. Relocate junction box and associated plugs and grommets
to opposite side panel. Secure with screws removed in
step 2.
STANDARD
JUNCTION BOX
LOCATION
Junction Box Relocation
T
O AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR DEATH, THE FURNACE
MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR,
IN THEIR ABSENCE, WITH THE LATEST EDITION OF THE
C
ODE.
To ensure proper unit grounding, the ground wire should run from
the furnace ground screw located inside the furnace junction box all
the way back to the electrical panel. NOTE: Do not use gas piping
as an electrical ground. To confirm proper unit grounding, turn off
the electrical power and perform the following check.
1. Measure resistance between the neutral (white) connection
and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch which
interrupts unit voltage when the blower door is opened for servic-
ing. Do not defeat this switch.
24 V
T
W
OLT
HERMOSTAT
IRING
NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance.
Low voltage connections can be made through either the right or
left side panel. Thermostat wiring entrance holes are located in the
blower compartment. Wire routing must not to interfere with circu-
lator blower operation, filter removal, or routine maintenance. Re-
fer to the following figure for thermostat connections to the inte-
grated control module terminal strip.
Y
W
W
R
R
G
C
HEATING
ROOM
FURNACE
THERMOSTAT
Thermostat Diagram
This furnace is equipped with a 40 VA transformer to facilitate use
with most cooling equipment. Consult the wiring diagram, located
on the blower compartment door, for further details of 115 Volt and
24 Volt wiring.
ALTERNATE
JUNCTION BOX
LOCATION
WARNING
N
E
ATIONAL
LECTRIC
Y
W
Y
W
Y
R
C
G
R
G
C
HEATING AND
REMOTE
FURNACE
COOLING ROOM
CONDENSING
THERMOSTAT
UNIT

115 V

L
C
OLT
INE
ONNECTION OF
E
A
C
AND
LECTRONIC
IR
LEANER
T
O AVOID INJURY, ELECTRICAL SHOCK OR DEATH, DISCONNECT ELECTRICAL
POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING.
The furnace's integrated control module is equipped with line volt-
age accessory terminals for controlling power to an optional field-
supplied humidifier and/or electronic air cleaner.
The accessory load specifications are as follows:
Humidifier
Electronic Air Cleaner
Turn OFF power to the furnace before installing any accessories.
Follow the humidifier or air cleaner manufacturers' instructions for
locating, mounting, grounding, and controlling these accessories.
Accessory wiring connections are to be made through the 1/4" quick
connect terminals provided on the furnace integrated control mod-
ule. The humidifier and electronic air cleaner hot and neutral termi-
nals are identified as HUM and EAC. All field wiring must conform to
applicable codes. Connections should be made as shown below.
OPTIONAL
ACCESSORIES
120 VAC
HOT AND
PARK
TERMINALS
12 PIN
CONNECTOR
Accessories Wiring
If it is necessary for the installer to supply additional line voltage
wiring to the inside of the furnace, the wiring must conform to all
local codes, and have a minimum temperature rating of 105°C. All
line voltage wire splices must be made inside the furnace junction
box.
The integrated control module humidifier terminals (HUM) are en-
ergized with 115 volts whenever the induced draft blower is ener-
gized. The integrated control module electronic air cleaner termi-
nals (EAC) are energized with 115 volts whenever the circulator
blower is energized.
24 V
H
OLT
UMIDIFIER
A 1/4" piggy back quick connect terminal on the pressure switch
provides 24VAC humidifier control. This terminal is powered any
time the pressure switch closes. To connect 24VAC HUM, connect
the 24VAC line of the humidifier to the piggyback on the pressure
switch and the COM line of the humidifier to C on the control board
terminal strip (or to the COM side of the 24VAC transformer). Do
not connect 115V humidifier to these terminals.
XII. GAS SUPPLY AND PIPING
G
ENERAL
The furnace rating plate includes the approved furnace gas input
rating and gas types. The furnace must be equipped to operate on
the type of gas applied. This includes any conversion kits required
for alternate fuels and/or high altitude.
22
A
(H
CCESSORIES
UMIDIFIER
)
WARNING
1.0 Amp maximum at 120 VAC
1.0 Amp maximum at 120 VAC
ELECTRONIC
AIR CLEANER
HUMIDIFIER
HUM-N
EAC-N
INTEGRATED
120 VAC
CONTROL
NEUTRAL
TERMINALS
MODULE