Performing sensor detection sensitivity tests
Test 1: Vacancy test
To start Test 1, touch [Test 1].
Ten seconds later, the vacancy detection
test will automatically begin.
This test will test for the presence of
noise that leads to false detection.
Leave the room within 10 seconds after
touching the button, and leave the room
unoccupied for 1 minute until the test is
completed.
When the test is complete, the result
will be displayed in color on the LED
indicator.
• Blue: Normal (The sensor correctly
detected vacancy without being
interfered with by noise.)
• Red: Error (The sensor falsely detected
occupancy due to noise.)
If the sensor failed to correctly detect
vacancy, lower the detection sensitivity
level and try again.
The sensor detection area is as follows: 110° to either side, 32 feet (10 meters).
Some conditions will render the sensor susceptible to false detection.
Refer to "How To Install" in chapter 1 in the Installation Manual.
Test 2: Occupancy test
To start Test 2, touch [Test 2].
When movements are detected, the LED
indicator will light up in blue.
Walk away from the remote controller,
and walk around in areas where you
want the sensor to detect motions to see
if it will respond correctly.
If the sensor does not respond, raise the
detection sensitivity level and try again.